Edwards Signaling EBPS Remote Booster Power Supply User Manual
Page 39
Remote Booster Power Supply Technical Reference Manual
33
Legend
(1) NAC1/AUX1
(2) NAC2/AUX2
(3) NAC3/AUX3
(4) NAC4/AUX4
(5)
200 mA AUX Continuous
(6) Sense 1 IN
(7) Sense
1
COM
(8) Sense
1OUT
(9) Sense 2 IN
(10) Sense
2
COM
(11) Sense
2
OUT
(12) Trouble NO
(13) Trouble
COM
(14) Trouble
NC
(15) Notification appliance circuit (NAC)
(16) UL listed EOL 15 kΩ
(17) From existing fire alarm panel
notification circuit or CC1(S) module
(18) Out to EOL or next device
(19) NAC
circuit
(20) UL listed EOL 15 kΩ
(21) Data out to next device
(22) Data in from previous device or
Signature controller
(23) NAC circuit
(24) UL listed EOL 15 kΩ
(25) EOL 15 kΩ, when used as a NAC
(26) UL listed EOL relay
(27) EOL 47 kΩ
Notes
•
When a booster power supply output is programmed as an AUX output, a listed EOL relay
(PAM1, 6254A-003, or 73402A) or equivalent must be used to supervise the AUX output.
•
When a booster power supply output is programmed as an NAC output, a 15 kΩ EOL resistor
must be used for supervision.