Installation instructions, Maintenance – Edwards Signaling Genesis Chime User Manual
Page 2
![background image](/manuals/366903/2/background.png)
2 / 2
27MAY03
P/N: 3100561 REV: 1.0
Table 2: Operating current in (Amp RMS)
High
db
Low
db
16 Vdc
0.030
0.019
24 Vdc
0.043
0.026
33 Vdc
0.045
0.027
16 Vfwr
0.060
0.040
24 Vfwr
0.076
0.049
33 Vfwr
0.081
0.055
Vdc = Volts direct current, regulated and filtered
Vfwr = Volts full wave rectified.
Table 3: Sound level output (dBA)
Signal and voltage
High db
Low db
16 Vdc
56.9
52.5
24 Vdc
59.8
54.8
Temporal
33 Vdc
60.1
55.0
16 Vdc
58.2
52.8
24 Vdc
60.8
55.6
Steady
33 Vdc
61.3
56.1
dBA = Decibels, A-weighted
UL464: Sound level output at 10 ft (3.05 m) measured in a
reverberant room.
Installation instructions
Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field
wires around the terminals.
To install the chime:
1. Remove the cover by depressing both tabs on the top of
the unit with a small screwdriver and twisting slightly.
2. Set the chime signal, sound output level, and desired
operation settings. See Figure 1.
3. Connect the chime terminals to the signal circuit field
wiring. You must observe polarity for the unit to function
properly.
For constant non-coded voltage operation, see Figure 2.
For single-stroke coded voltage operation, see Figure 3.
4. Mount the unit onto a compatible electrical box, making
sure not to over tighten the mounting screws.
5. Replace the cover by aligning at the bottom, then
snapping in at the top.
6. Test the unit for proper operation.
Maintenance
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
J2 J3
J1
To change the chime
from steady to temporal cut
from circle J1 to edge of
circuit board
signal
To change the chime
from non-coded to coded (single-
stroke)
operation
cut from circle J2 to edge
of circuit board
To change the chime
from high dB to
low dB cut J3 trace between
holes
sound
output level
Figure 1: Chime settings
Note: Polarity shown in alarm condition
To next device or
end of line device
-
+
-
+
From compatible fire
alarm control panel
+
-
+
-
Figure 2: Constant non-coded voltage operation
Genesis device with
Genesis Signal Master
[1]
-
+
HS
-
+
To next device or
end of line device
Continuous
power source
Coded power
source
+
+
-
-
+
-
Figure 3: Single-stroke coded voltage operation