beautypg.com

Edwards Signaling 125 Class Incand User Manual

Page 2

background image

P/N 3101757 ISSUE 3

Figure 1. Conduit Mounting (3/4" Shown)

125 Class

Visual Indicator

Connect leads to

Power Source

3/4” NPT external (shown)

1/2” NPT internal

Conduit (not supplied)

DC units; Red positive (+)

AC units; Black Hot

DC units; Black negative (-)

AC units; White neutral

Wire nuts

(not supplied)

18” Wire Leads

Figure 3. Lamp Replacement

Lens

Incandescent Lamp

Lamp Socket

O-Ring (in groove)

(supplied)

Base

(4) Screws securiing

lens to base

Table 1. Replacement Parts

Catalog Number

(gray base)

Catalog Number

(black base)

Replacement

Lens

Replacement Lamp

Flashing Incandescent

125INCF*24D

125INCF*24DB

125L*

Industry Trade 1692

125INCF*120A

125INCF*120AB

Industry Trade 15T7DC

Steady-On Incandescent

125INCS*24D

125INCS*24DB

125L*

Industry Trade 1692

125INCS*120A

125INCS*120AB

Industry Trade 15T7DC

*Letter in this position indicates lens color: A - Amber, B - Blue, C - Clear, G - Green, R - Red.

Figure 2. Panel Mounting

125 Class

Visual Indicator

Gasket

(supplied)

Locking Nut -

1.3625" OD

(supplied)

Control panel

(enclosure)

Wire Nuts

(Not Supplied)

18” Wire Leads

Power Source

Wires

Table 2. Programming Logic Controller (PLC) Compatibility: PLC Output to meet following product input parameters

Cat. No.*

Operating voltage

(Volts)

Max. off state leak-

age current (mA)

Continuous on

current (mA)

Repetitive

Surge

Surge

(inrush/duration)

125INCF24D

24V DC

25

25

0.68A

7A exp decaying

125INCF120A

120V AC 50/60 Hz

25

25

0.3A / 8 ms

0.8A exp decaying

125INCS24D

24V DC

25

25

2.5A / 60 ms

7A exp decaying

125INCS120A

120V AC 50/60 Hz

25

25

0.5A / 8 ms

0.8A exp decaying

*PLC compatibility applies to models with any lens color and with either a gray or black base.