Edwards Signaling 125 Class Incand User Manual
Page 2
P/N 3101757 ISSUE 3
Figure 1. Conduit Mounting (3/4" Shown)
125 Class
Visual Indicator
Connect leads to
Power Source
3/4” NPT external (shown)
1/2” NPT internal
Conduit (not supplied)
DC units; Red positive (+)
AC units; Black Hot
DC units; Black negative (-)
AC units; White neutral
Wire nuts
(not supplied)
18” Wire Leads
Figure 3. Lamp Replacement
Lens
Incandescent Lamp
Lamp Socket
O-Ring (in groove)
(supplied)
Base
(4) Screws securiing
lens to base
Table 1. Replacement Parts
Catalog Number
(gray base)
Catalog Number
(black base)
Replacement
Lens
Replacement Lamp
Flashing Incandescent
125INCF*24D
125INCF*24DB
125L*
Industry Trade 1692
125INCF*120A
125INCF*120AB
Industry Trade 15T7DC
Steady-On Incandescent
125INCS*24D
125INCS*24DB
125L*
Industry Trade 1692
125INCS*120A
125INCS*120AB
Industry Trade 15T7DC
*Letter in this position indicates lens color: A - Amber, B - Blue, C - Clear, G - Green, R - Red.
Figure 2. Panel Mounting
125 Class
Visual Indicator
Gasket
(supplied)
Locking Nut -
1.3625" OD
(supplied)
Control panel
(enclosure)
Wire Nuts
(Not Supplied)
18” Wire Leads
Power Source
Wires
Table 2. Programming Logic Controller (PLC) Compatibility: PLC Output to meet following product input parameters
Cat. No.*
Operating voltage
(Volts)
Max. off state leak-
age current (mA)
Continuous on
current (mA)
Repetitive
Surge
Surge
(inrush/duration)
125INCF24D
24V DC
25
25
0.68A
7A exp decaying
125INCF120A
120V AC 50/60 Hz
25
25
0.3A / 8 ms
0.8A exp decaying
125INCS24D
24V DC
25
25
2.5A / 60 ms
7A exp decaying
125INCS120A
120V AC 50/60 Hz
25
25
0.5A / 8 ms
0.8A exp decaying
*PLC compatibility applies to models with any lens color and with either a gray or black base.