Chapter 2
Installation
Panel Installation
1. Prepare a mounting panel cutout by cutting a rectangular
hole (3.62” +0.02/-0.0” X 1.77” + 0.02/-0.0”) in the
desired location (see Figure following page). The
maximum panel thickness is 3/8 inches.
2. Remove the mounting bracket from the instrument
housing by removing the two screws on the rear of the
indicator..
3. Remove the pluggable terminal block located at the rear of
the unit and wire the input power and RS232 wires. If an
option board is installed in the indicator, remove the
connector and make the appropriate connections (refer
to diagrams).
WARNING!
Dangerous voltages are exposed at the screw
terminals. Always remove power before working in
this area for rewiring, disassembly, and all other
activities that involve proximity to electrical