digit flashing. With the ARROW key select the number 0.
Press ENT. The second digit will flash. Enter 0 again with
the ARROW key. Continue on until 0032 is on the display
with the 2 flashing. Press ENT.

STEP 4.

HIGH will appear on the display. Press ENT. Set

the first digit to 0 by using the ARROW button. Set the
second digit to 5 and so on until 0500 is on the display. With
the farthest digit to the right flashing, press ENT. The next
menu item appears.

Example2:

Program the indicator to output 0.0 VDC at

0

°

F and 5VDC at 1000

°

F.

Note: The analog output may be scaled to output
various voltages such as 0-2VDC, 1-5VDC etc.

STEP 1.

Press the PGM button. PGM will appear on the

display. The

°

F/

°

C LED will change to P (for ‘Program

Mode).

STEP 2.

Press the Arrow key until ALOG appears on the

display. Open the ALOG Menu for programming by pressing
the ENT key.

STEP 3.

A LOW or HIGH will appear. Pressing the Arrow

key repeatedly will cause LOW and HIGH to alternate on the
display. With LOW on the display, select LOW by pressing
the ENT key. The digits 0000 will appear with the left most
digit flashing. With the ARROW key select the number 0.