background image

Model CX-IR

Table 3 CX-IR Register Map

Register

Name

R/W

Meaning

Units

40000

CX-IR Device Type

R

= 42

40001

Range

R/W

Detectable Range

%LEL

40002

Reading

R

Current Gas Reading

%LEL

40003

Calibration Level

R/W

Auto Span Level

%LEL

40004

Life

R

Sensor Life

%

40005

Sensor Faults

R

See Section 4.2.1

40006

Sensor Model

R

IR (set to 3)

40007

Days since Calibration

R

days

40008

Reserved

R

40009

Reserved

R

40010

Sensor Temperature

R

ºC

40011

Gas Factor

R/W

See Section 3.4.4

40012

Reserved

R

40013

Reserved

R

40014

Range Divisor

R

40015

Calibration Enable/Status

R/W

40016

Gas Type/Units String

R

ASCII Text (set at factory)

40017

Gas Type/Units String

R

ASCII Text (set at factory)

40018

Gas Type/Units String

R

ASCII Text (set at factory)

40019

Gas Type/Units String

R

ASCII Text (set at factory)

40020

Gas Type/Units String

R

ASCII Text (set at factory)

40021

Gas Type/Units String

R

ASCII Text (set at factory)


4.2.1 Sensor Faults – Register 40005


The sensor fault status register consists of High and Low Status Bits. These bits are set/reset as faults occur or
are cleared. Each Bit has a particular meaning and displayed as follows:

Register #

High Byte

Low Byte

0005

Status Bits

Status Bits

NOTE

Bits read as 0 are FALSE, bits read as 1 are TRUE.


Status Bits High Byte:
Bit 15 – Reserved
Bit 14 – Calibration Mode
Bit 13 – Reserved
Bit 12 – Zero Fault
Bit 11 – Range Fault
Bit 10 – Reserved
Bit 9

– Clearing Fault

Bit 8 – Reserved

Status Bits Low Byte:
Bit 7 – Sensor Fault
Bit 6

– Processor Fault

Bit 5

– Memory Fault

Bit 4

– Reserved

Bit 3

– Reserved

CX-IR Instruction Manual

Rev. 1.2

Page 23 of 34