1 sensor faults – register 40005, Sensor faults – register 40005, Table 3 cx-ir register map – Detcon CX-IR User Manual
Page 27
Model CX-IR
Table 3 CX-IR Register Map
Register
Name
R/W
Meaning
Units
40000
CX-IR Device Type
R
= 42
40001
Range
R/W
Detectable Range
%LEL
40002
Reading
R
Current Gas Reading
%LEL
40003
Calibration Level
R/W
Auto Span Level
%LEL
40004
Life
R
Sensor Life
%
40005
Sensor Faults
R
See Section 4.2.1
40006
Sensor Model
R
IR (set to 3)
40007
Days since Calibration
R
days
40008
Reserved
R
40009
Reserved
R
40010
Sensor Temperature
R
ºC
40011
Gas Factor
R/W
See Section 3.4.4
40012
Reserved
R
40013
Reserved
R
40014
Range Divisor
R
40015
Calibration Enable/Status
R/W
40016
Gas Type/Units String
R
ASCII Text (set at factory)
40017
Gas Type/Units String
R
ASCII Text (set at factory)
40018
Gas Type/Units String
R
ASCII Text (set at factory)
40019
Gas Type/Units String
R
ASCII Text (set at factory)
40020
Gas Type/Units String
R
ASCII Text (set at factory)
40021
Gas Type/Units String
R
ASCII Text (set at factory)
4.2.1 Sensor Faults – Register 40005
The sensor fault status register consists of High and Low Status Bits. These bits are set/reset as faults occur or
are cleared. Each Bit has a particular meaning and displayed as follows:
Register #
High Byte
Low Byte
0005
Status Bits
Status Bits
NOTE
Bits read as 0 are FALSE, bits read as 1 are TRUE.
Status Bits High Byte:
Bit 15 – Reserved
Bit 14 – Calibration Mode
Bit 13 – Reserved
Bit 12 – Zero Fault
Bit 11 – Range Fault
Bit 10 – Reserved
Bit 9
– Clearing Fault
Bit 8 – Reserved
Status Bits Low Byte:
Bit 7 – Sensor Fault
Bit 6
– Processor Fault
Bit 5
– Memory Fault
Bit 4
– Reserved
Bit 3
– Reserved
CX-IR Instruction Manual
Rev. 1.2
Page 23 of 34