Figure 10 sensor wire connections, Table 1 wire gauge vs. distance, Figure 10 – Detcon DM-700 User Manual
Page 14
Model DM-700
DM-700 Instruction Manual
Rev. 4.0
Page 10 of 48
Table 1 Wire Gauge vs. Distance
AWG
Wire Dia.
Meters
Feet
Over-Current
Protection
22
0.723mm
700
2080
3A
20
0.812mm
1120
3350
5A
18
1.024mm
1750
5250
7A
16
1.291mm
2800
8400
10A
14
1.628mm
4480
13,440
20A
NOTE 1: Wiring table is based on stranded tinned copper wire and is designed to serve as a
reference only.
NOTE 2: Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.
NOTE 3: The supply of power should be from an isolated source with over-current protection
as stipulated in table.
Terminal Connections
CAUTION: Do not apply System power to the sensor until all wiring is properly terminated. Refer to
Section 2.7 Initial Start Up
Customer
Supplied Wiring
(Out to next Device)
(+
)
m
A
(-
)
A
(+
)
B
(-
)
Wiring to
Sensor Assembly
W
h
t
B
lu
R
e
d
G
rn
B
lk
Explosion
Proof
Junction Box
(+)
mA
(-)
A(+)
B(-)
(+)
mA
(-)
A(+)
B(-)
Customer
Supplied Wiring (In)
Modbus RS-485 to
Host Control Device
Power from and 4-20mA
out to Control Device
Install a 100-250 Ohm
resistor if the 4-20mA
output is not used
Modbus RS-485 to
next Device
Figure 10 Sensor Wire Connections
a) Remove the junction box cover. Identify the terminal blocks for customer wire connections.
b) Observing correct polarity, terminate the 3-conductor 4-20mA field wiring (+, -, mA) to the sensor
assembly wiring in accordance with the detail shown in Figure 10. If the 4-20mA output is not used,
install a 100-250Ω resistor between the mA and (-) terminals on the Transient Protection Module.