When mounting on a pole, secure the Junction Box to a suitable mounting plate and attach the mounting plate
to the pole using U-Bolts. (Pole-Mounting brackets for Detcon J-box accessories are available separately.)

3.675"

3/4" NPT

Explosion Proof Enclosure

Junction-Box

Sensor Assembly

Splash Guard

(Detcon's Junction-Box shown)

2.125"

5.5"

4.95"

5.25"

5.53"

2"

12.7"

M

o

u

n

ti

n

g

B

o

lt

Use Spacers to move

the J-Box and Sensor

Assembly away from the

wall at least 0.25-0.5" to

allow access to Sensor

W

a

ll

(o

r

o

th

e

r

m

o

u

n

ti

n

g

s

u

rf

a

c

e

)

8.06"

Ø0.265" x2

S

p

a

c

e

r

Mounting Holes

8-32 Thread

Ground Point

detcon inc.

CO2 Sensor

MODEL

DM-700

Figure 8 Outline and Mounting Dimensions

2.5 Electrical Installation

The Sensor Assembly should be installed in accordance with local electrical codes. The sensor assemblies are
CSA/NRTL approved (US and Canada) for Class I, Division 1, Groups B, C, & D area classifications, and are
ATEX Approved for Class I, Zone 1, Group IIC area classifications.

Proper electrical installation of the gas sensor is critical for conformance to Electrical Codes and to avoid
damage due to water leakage. Refer to Figure 9 and Figure 10 for proper electrical installation.

NOTE: If a conduit run exits the secondary port, repeat the installation technique shown in
Figure 9.

In Figure 9, the drain allows water condensation inside the conduit run to safely drain away from the sensor
assembly. The electrical seal fitting is required to meet the National Electrical Code per NEC Article 500-3d
(or Canadian Electrical Code Handbook Part 1 Section 18-154). Requirements for locations of electrical seals
are covered under NEC Article 501-5. Electrical seals also act as a secondary seal to prevent water from
entering the wiring terminal enclosure. However, they are not designed to provide an absolute water-tight
seal, especially when used in the vertical orientation.