RT‐15 Flow Monitor
Operation and Programming Manual
8
KFT
Scaling for display of total in specific engineering units. Determines display decimal resolution.
Initial value=10000. (pulses with no decimals)
KFT = 10000/K‐FACTOR
where K‐FACTOR is the avg. number of pulses/ eng. unit of the transducer.
Round result to desired decimal accuracy and enter KFT using only that number of decimal places. Use
no more than four digits regardless of decimal point position! Maximum = 65535 with the decimal in any
location.
ENG UNITS
The desired engineering units for display of total are programmable using up to four letters. Example:
GAL_
TOTAL RESET
With the cover removed and outside of a hazardous area use MODE/DN button to view TOTAL, and
RESET/UP button to reset.
GR TOTAL RESET
With cover open only! Use MODE/DN button and SEL button to view GR TOTAL, press RESET/UP button
plus ENT button. Use SEL button for “Y”; press ENT to reset and exit.
Product Description
The RT‐15 is a meter‐mounted digital flow monitor housed in a hazardous‐location rated enclosure.
The unit’s large, backlighted LCD display makes it easy to monitor flow rate and total in your choice
of engineering units. A variety of sensor noses make the RT‐15 compatible with many of the flow
meters available from AW Gear Meters.
Access Information and Make Changes
You can make program or mode changes, or reset the totalizer in two ways. When the faceplate is
open, enter information using pushbuttons; when the faceplate is closed, use a magnet wand to
make changes.
You can also reset the totalizer, and monitor flow rate limits and total output remotely via a
computer or PLC.