User’s guide, Battery management system – APC Battery Management System User Manual
Page 105

®
USER’S GUIDE
Battery Management System
98
0x0821
Informational
Battery: Dryout/sulfation no longer present.
0x0822
Severe
Battery: Pilot temperature high.
0x0823
Informational
Battery: High pilot temperature returned to normal.
0x0824
Severe
Environment: Ambient temperature high.
0x0825
Informational
Environment: High ambient temperature returned to normal.
0x0826
Warning
Environment: Ambient temperature low.
0x0827
Informational
Environment: Low ambient temperature returned to normal.
0x0828
Severe
Management Controller: System is not configured correctly.
0x0829
Informational
Management Controller: System is configured correctly.
0x082A
Warning
Management Controller: Ripple current sensor is
disconnected.
0x082B
Informational
Management Controller: Ripple current sensor is present.
0x082C
Severe
Management Controller: Current sensor is disconnected.
0x082D
Informational
Management Controller: Current sensor is present.
0x082E
Severe
Management Controller: Pilot temperature sensor is
disconnected.
0x082F
Informational
Management Controller: Pilot temperature sensor is present.
0x0830
Warning
Management Controller: Ambient temperature sensor is
disconnected.
0x0831
Informational
Management Controller: Ambient temperature sensor is
present.
0x0832
Informational
System: Response benchmark established.
0x0833
Informational
System: Response test complete.
Code
Severity
Description