Setup Items in Setting Mode and Their Default Values

(Recorder version: 1.31)

The items with an asterisk are not displayed in the default condition. To display these
items, settings must be changed in Basic Setting mode.

Setup Item

Pen/Dot

Selectable Range or Selections

Default Value

Range > CH

-

01 to 24

01

Range > Mode

-

Volt/TC/RTD/1-5V/Scale/Delta/DI/SQRT/Skip

Volt

Range > Mode > Range

-

20mV/60mV/200mV/2V/6V/20V/50V/1-5V/

R/S/B/K/E/J/T/N/W/L/U/WRe/Pt/JPt/Level/Cont/

(Slections for /N1 and /N3 options)

2V

*Bias > CH

-

01 to 24

01

*Bias > Bias

-

On/Off

Off

*Bias > Bias

-

±10 % of the span of the measurable range

-

Calibration (/CC1 option)
Calibration > CH

-

01 to 24

01

Calibration > Calibration

-

On/Off

Off

Calibration > datums

-

Within the range

-

Calibration > revise

-

Within the range

(correction point + correction value for revise value)

-

Calibration > Decision

-

Yes/No

Yes

Alarm > CH

-

01 to 24

01

Alarm > Level

-

1/2/3/4

1

Alarm > Alarm

-

On/Off

Off

Alarm > Type

-

H/L/h/l/R/r (*/T/t)

H

Alarm > Value

-

Depends on the alarm type.

-

Alarm > Relay

-

On/Off

Off

Alarm > Relay number

-

I01 to I06, I11 to I16, I21 to I26, I31 to I36

I01

Unit > CH

-

01 to 24

01

Unit > Unit

-

6 characters or less

Blank

Chart

Pen Model 82 types (pen model)

25 mm/h

Dot Model

1 to 1500 mm/h (dot model)

25 mm/h

Clock

-

Date/Time

-

Aux > Trend

Dot Model

Auto/Fix

Auto

Aux > Zone > CH

-

01 to 24

01

Aux > Zone > Left, Right

-

Within the recording span range (mm)

Left: 0, Right: 180

*Aux > Partial > CH

-

01 to 24

01

*Aux > Partial > Partial

-

On/Off

Off

*Aux > Partial > Expand

-

1 to 99%

50

*Aux > Partial > Boundary

-

Within the recording span range

-

Aux > Print out > CH

-

01 to 24

01

Aux > Print out > Trend

Dot Model

On/Off

On

Aux > Print out > Periodic

-

On/Off

On

Aux > Tag > CH

-

01 to 24

01

Aux > Tag > Tag

-

7 characters or less

01 to 24

Aux > Message > Message number

-

1 to 5

1

Aux > Message > (Message)

-

16 characters or less

Blank

Aux > Chart2

Pen Model 82 types (pen model)

25 mm/h

Dot Model

1 to 1500 mm/h (dot model)

25 mm/h

*Aux > Moving_AVE > CH

Dot Model

01 to 24

01

*Aux > Moving_AVE > number of samples Dot Model

Off, 2 to 16

Off

*Aux > Filter > CH

Pen Model 01 to 24

01

*Aux > Filter > Response time

Pen Model 2s/5s/10s

Off

*Aux > Alarm delay time > CH

-

01 to 24

01

*Aux > Alarm delay time > Duration

-

0 to 3600s

10s

Aux > Brightness > Display

-

1/2/3/4/5/6/7/8

4

Aux > Brightness > Light

-

1/2/3/4

2

Aux > DST

-

Not/Use

Not

Aux > DST > Start month

-

Apr/May/Jun/Jul/Aug/Sep/Oct/Nov/Dec/Jan/Feb/Mar Apr

Aux > DST > Strt day

-

1st-Sun/.../Last-Mon

1st-Sun

Aux > DST > Start time

-

0:00 to 23:00

0:00