Setting the Input Range and Alarm on Measurement

Channels

Setup Example (1) of Thermocouple Input

Set channel 02 to thermocouple type K and measure temperatures in the range –50.0 to
450.0°C. The measurable range for thermocouple type K is –200.0 to 1370.0°C.
The measured values in the range of –50.0 to 450.0°C are recorded in a width of 180 mm
on the chart paper. This recording range is called a recording span, and the leftmost and
rightmost values of the recording span are called span left and span right, respectively.

–200.0°C

1370.0°C

Measurable range of thermocouple type K

–50.0°C

450.0°C

(Span left)

180 mm

(Span right)

Chart paper

Entering Setting Mode

1.

Hold down the

MENU

key for 3 seconds to enter Setting mode.

Selecting the Range

2.

Press the key with

Range shown on the screen.

Set=Range

Input range and record

Displays a description of the setup item.

Selecting the Channel Range

3.

Press the

key to set the first channel to

02 and then press the key.

First channel Last channel

CH=02-02

First channel 01-06

Displays the selectable range of channels.

4.

Likewise, set the last channel to

02 and then press the key.

Selecting the Input Type

5.

Press the

key to select

TC and then press the key (see “Explanation” on

page 40).

Mode=TC

Thermocouple

6.

Press the

key to select

K and then press the key.

Range=K

R,S,B,K,E,J,T,N,W,L,U,

Displays the thermocouple type.

Setting Span Left

7.

Set Span left to

–50.0 and press the key.

Press the

key to select the desired digit.

Press the

key to select the value.

Span left= -50.0

-200.0/ 1370.0°C

Displays the measurable range of

thermocouple type K.

* When the key or key is pressed while holding down the

SHIFT key, the operation is reversed as

when the respective key is pressed by itself.