Communication (serial) > basic settings – Yokogawa Button Operated MV2000 User Manual
Page 56
Communication (Ethernet) > Modbus client > Modbus server settings
Setting
Selectable Range or Choices
Default Value
Server number
1-8/9-16
1-8
Port
Numeric value (0 to 65535)
502
Modbus server name
Character string (up to 64 characters)
—
Unit
Auto/Fixed
Auto
No.
0 to 255
1
Communication (Ethernet) > Modbus client > Command settings
Setting
Selectable Range or Choices
Default Value
Master command number
1-8/9-16
1-8
1 to 16
Off/R-M/W/W-M
Off
First
Varies depending on the send command type
—
Last
Varies depending on the send command type
—
Server
1/2/3/…/15/16
1
Regi.
Numeric value (register number)
R-M:30001
W, W-M: 40001
Type
INT16/UINT16/INT32_B/INT32_L/UINT32_B/
R-M, W: INT16
UINT32_L/FLOAT_B/FLOAT_L
W-M: INT32_B
Communication (Serial) > Basic settings
Setting
Selectable Range or Choices
Default Value
Serial
Baud rate
1200/2400/4800/9600/19200/38400
9600
Data length
7/8
8
Parity
Odd/Even/None
Even
Handshaking
Off:Off/XON:XON/XON:RS/CS:RS
Off:Off
Address
Numeric value (1 to 99)
1
Protocol
Normal/Modbus/Modbus-M
Normal
Communication (Serial) > Modbus master > Basic settings
Setting
Selectable Range or Choices
Default Value
Modbus master basic settings
Read cycle
125ms/250ms/500ms/1s/2s/5s/10s
1s
Timeout
125ms/250ms/500ms/1s/2s/5s/10s/1min
1s
Retrials
Off/1/2/3/4/5/10/20
1
Inter-block delay
Off/5ms/10ms/15ms/45ms/100ms
Off
Auto recovery
Off/1min/2min/5min/10min/20min/30min/1h
2min
Communication (Serial) > Modbus master > Command settings
Setting
Selectable Range or Choices
Default Value
Master command number
1-8/9-16
1-8
1 to 16
Off/R-M/W/W-M
Off
First
Varies depending on the send command
—
Last
Varies depending on the send command
—
Addr.
Numeric value (1 to 247)
1
Regi.
Numeric value (register number)
R-M: 30001
W, W-M: 40001
Type
INT16/UINT16/INT32_B/INT32_L/UINT32_B/
R-M, W: INT16
UINT32_L/FLOAT_B/FLOAT_L
W-M: INT32_B
Default MV1000 Settings
56
IM MV1000-02E