Setting mode settings and default values, Setting mode settings and default values menu tab, Meas channel > range, alarm – Yokogawa Button Operated MV2000 User Manual
Page 39
Setting Mode Settings and Default Values
Menu Tab
Meas channel > Range, Alarm
Setting
Selectable Range or Choices
Default Value
First-CH, Last-CH
Numeric value (channel number) 1 to 24
1
Range > Mode
Skip/Volt/TC/RTD/Scale/Delta/DI/1-5V/Sqrt
Volt
Volt
Range
20mV/60mV/200mV/2V/6V/20V/50V
2V
Span_L
Numeric value (depends on the range)
–2.0000
Span_U
Numeric value (depends on the range)
2.0000
TC
Range
R/S/B/K/E/J/T/N/W/L/U/WRe
R
Span_L
Numeric value (depends on the range)
0.0
Span_U
Numeric value (depends on the range)
1760.0
RTD
Range
Pt/JPt
Pt
Span_L
Numeric value (depends on the range)
–200.0
Span_U
Numeric value (depends on the range)
600.0
Scale
Type
Volt/TC/RTD/DI
Volt
Range
20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)
2V
R
Pt
Level
Span_L
Numeric value (depends on the range)
–2.0000
Span_U
Numeric value (depends on the range)
2.0000
Scale_L
Numeric value (depends on the range)
0.00
Scale_U
Numeric value (depends on the range)
200.00
Unit
Character string (up to 6 characters)
—
Mode = Delta
Type
Volt/TC/RTD/DI
Volt
Range
20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)
2V
R
Pt
Level
Span_L
Numeric value (depends on the range)
–2.0000
Span_U
Numeric value (depends on the range)
2.0000
Ref. CH
Numeric value (measurement channel number)
001
Mode = DI
Range
Level/Cont
Level
Span_L
Numeric value (0, 1)
0
Span_U
Numeric value (0, 1)
1
Mode = 1-5V
Range
1-5V
1–5V
Span_L
Numeric value (0.800 to 5.200)
1.000
Span_U
Numeric value (0.800 to 5.200)
5.000
Scale_L
Numeric value (–30000 to 30000, Decimal place 0 to 4) 0.00
Scale_U
Numeric value (–30000 to 30000, Decimal place 0 to 4) 200.00
Unit
Character string (up to 6 characters)
—
Low-cut
On/Off
Off
Mode = Sqrt
Range
20mV/60mV/200mV/2V/6V/20V/50V
2V
Span_L
Numeric value (depends on the range)
–2.0000
Span_U
Numeric value (depends on the range)
2.0000
Scale_L
Numeric value (–30000 to 30000, Decimal place 0 to 4) 0.00
Scale_U
Numeric value (–30000 to 30000, Decimal place 0 to 4) 200.00
Unit
Character string (up to 6 characters)
—
Low-cut
On/Off
Off
Value
0.0 to 5.5 %
0.5
Range > Alarm 1 to 4
On/Off
Off
Default MV1000 Settings
39
IM MV1000-02E