beautypg.com

Setting mode settings and default values, Setting mode settings and default values menu tab, Meas channel > range, alarm – Yokogawa Button Operated MV2000 User Manual

Page 39

background image

Setting Mode Settings and Default Values

Menu Tab

Meas channel > Range, Alarm

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 24

1

Range > Mode

Skip/Volt/TC/RTD/Scale/Delta/DI/1-5V/Sqrt

Volt

Volt

Range

20mV/60mV/200mV/2V/6V/20V/50V

2V

Span_L

Numeric value (depends on the range)

–2.0000

Span_U

Numeric value (depends on the range)

2.0000

TC

Range

R/S/B/K/E/J/T/N/W/L/U/WRe

R

Span_L

Numeric value (depends on the range)

0.0

Span_U

Numeric value (depends on the range)

1760.0

RTD

Range

Pt/JPt

Pt

Span_L

Numeric value (depends on the range)

–200.0

Span_U

Numeric value (depends on the range)

600.0

Scale

Type

Volt/TC/RTD/DI

Volt

Range

20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)

2V
R
Pt
Level

Span_L

Numeric value (depends on the range)

–2.0000

Span_U

Numeric value (depends on the range)

2.0000

Scale_L

Numeric value (depends on the range)

0.00

Scale_U

Numeric value (depends on the range)

200.00

Unit

Character string (up to 6 characters)

Mode = Delta

Type

Volt/TC/RTD/DI

Volt

Range

20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)

2V
R
Pt
Level

Span_L

Numeric value (depends on the range)

–2.0000

Span_U

Numeric value (depends on the range)

2.0000

Ref. CH

Numeric value (measurement channel number)

001

Mode = DI

Range

Level/Cont

Level

Span_L

Numeric value (0, 1)

0

Span_U

Numeric value (0, 1)

1

Mode = 1-5V

Range

1-5V

1–5V

Span_L

Numeric value (0.800 to 5.200)

1.000

Span_U

Numeric value (0.800 to 5.200)

5.000

Scale_L

Numeric value (–30000 to 30000, Decimal place 0 to 4) 0.00

Scale_U

Numeric value (–30000 to 30000, Decimal place 0 to 4) 200.00

Unit

Character string (up to 6 characters)

Low-cut

On/Off

Off

Mode = Sqrt

Range

20mV/60mV/200mV/2V/6V/20V/50V

2V

Span_L

Numeric value (depends on the range)

–2.0000

Span_U

Numeric value (depends on the range)

2.0000

Scale_L

Numeric value (–30000 to 30000, Decimal place 0 to 4) 0.00

Scale_U

Numeric value (–30000 to 30000, Decimal place 0 to 4) 200.00

Unit

Character string (up to 6 characters)

Low-cut

On/Off

Off

Value

0.0 to 5.5 %

0.5

Range > Alarm 1 to 4

On/Off

Off

Default MV1000 Settings

39

IM MV1000-02E

This manual is related to the following products: