Burnout, rjc, Keylock > password, key action, media, Keylock > action of function – Yokogawa Button Operated MV2000 User Manual
Page 51: Login > basic settings, Login > admin settings
A/D, Memory
Setting
Selectable Range or Choices
Default Value
Scan interval > Scan mode
Normal/Fast
Normal
Normal > Scan interval
125ms/250ms (MV1004, MV1008)
125ms
1s/2s/5s (MV1006, MV1012, MV1024)
1s
Normal > A/D integrate
Auto/50Hz/60Hz
Auto
Fast > Scan interval
25ms (MV1004, MV1008)
25ms
125ms (MV1006, MV1012, MV1024)
125ms
Fast > A/D integrate
600Hz
600Hz
Memory
Data kind
Display/E+D/Event
Event
Burnout, RJC
Setting
Selectable Range or Choices
Default Value
First-CH, Last-CH
1/2/3/…/23/24 (varies depending on the model)
1
Burnout set
Off/Up/Down
Off
RJC
Mode
Internal/External
Internal
Volt
Numeric value (–20000 to 20000)µV
0
Keylock > Password, Key action, Media
Setting
Selectable Range or Choices
Default Value
Password
Character string (up to 8 characters)
********
Key action
START/STOP
Free/Lock
Free
HISTORY
Free/Lock
Free
MENU
Free/Lock
Free
USER
Free/Lock
Free
DISP/ENTER
Free/Lock
Free
T/DIV
Free/Lock
Free
Media/USB
External media
Free/Lock
Free
Load settings
Free/Lock
Free
Keylock > Action of Function
Setting
Selectable Range or Choices
Default Value
Action of Function
Character string (up to 8 characters)
********
AlarmACK
Free/Lock
Free
Message/Batch
Free/Lock
Free
Math
Free/Lock
Free
Data save
Free/Lock
Free
E-mail/FTP
Free/Lock
Free
Time set
Free/Lock
Free
Display Function
Free/Lock
Free
Login > Basic settings
Setting
Selectable Range or Choices
Default Value
User basic settings
Auto logout
Off/1min/2min/5min/10min
Off
Operation without Login
Off/Display
Off
Login > Admin settings
Setting
Selectable Range or Choices
Default Value
Admin number
1/2/3/4/5
1
Mode
Off/Key/Key+Comm
Off
User name
Character string (up to 20 characters)
Admin1, etc.
Password
Character string (up to 8 characters)
????????
Default MV1000 Settings
51