A.3.1 data display with bt200, A.3.2 data setting with bt200 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual
Page 34

IM 01C50T03-01E
A-5
APPENDIX A. OPERATION OF BRAIN TERMINAL BT200
A.3.1 Data Display with BT200
The following procedure is used to display data on the
BT200 screen.
PARAM
01:MODEL
YTA320
02:TAG NO.
YOKOGAWA
03:SELF CHECK
GOOD
OK
MENU
A:VARIABLE
B:SET VAL CON.
HOME SET ADJ ESC
PARAM
A10:PV
125.06 degC
A11:mA of RANGE
16.51 mV
A12:% of RANGE
50.25 %
DATA DIAG PRNT ESC
PARAM
A10:PV
125.06 degC
A11:mA of RANGE
16.51 mV
A12:% of RANGE
50.25 %
DATA DIAG PRNT ESC
[STARTUP SCREEN]
Display
Description
[INITIAL DATA SCREEN]
[HOME MENU SCREEN]
[PARAMETER SCREEN]
––WELCOME––
BRAIN TERMINAL
ID: BT200
check connection
push ENTER key
UTIL FEED
F0A09.EPS
Displays the model name, the
tag number, and diagnostics
information. Press the
(OK) key after confirmation.
(The text specified upon order
is set for TAG.)
Execution of function keys
While the highlight bar is at A:
VARIABLE, press the
key to enter the parameter
display.
• A maximum 3 items of data
is displayed on one screen.
• Communication is executed
at 5-second intervals. (Data
is updated in a 5-second
cycle.)
• Use
for page forward and item
selection.
F1 : Updates the current data.
Pressing this key forces
communication with the
connected equipment and
the data of the equipment
is read and displayed.
F2 : Displays the self-
diagnosis screen.
F3 : Displays the parameter
print screen.
F4 : Returns to the previous
screen (the menu screen)
Press the
key to turn
on the BT200.
“Please wait...” is displayed for
several seconds and [Start
display] is displayed.
Connect YTA and BT200 using
a communication cable and
press the key.
A.3.2 Data Setting with BT200
The following procedure is used to change YTA data
settings.
●
Example: Changing C10 TAG to “FIC-la.”
[STARTUP SCREEN]
[INITIAL DATA SCREEN]
[HOME MENU SCREEN]
[SET MENU SCREEN]
[PARAMETER SCREEN]
––WELCOME––
BRAIN TERMINAL
ID: BT200
check connection
push ENTER key
UTIL FEED
PARAM
01:MODEL
YTA320
02:TAG NO.
YOKOGAWA
03:SELF CHECK
GOOD
MENU
A:VARIABLE
B:SET VAL CON.
HOME
SET
ADJ
MENU
C.SET TAG
D.SET SENSOR1
E.SET SENSOR2
E.SET OUTPUT
F.FORCED OUT
H:SET MODE
HOME
SET
ADJ
MENU
C10:TAG
YOKOGAWA
C60:SELF CHECK
GOOD
DATA
DIAG
PRNT
F0A10.EPS
Display
Description
Displays the model name, the
tag number, and diagnostics
information. Press the
(OK) key after confirmation.
(The text specified upon order
is set for TAG.)
Press the (SET) key to
display SET menu panel.
Select C: SETTING and press
the key.
Press the
key to turn on
the BT200.
“Please wait...” is displayed for
several seconds and [Start
display] is displayed.
Connect YTA and BT200 using
a communication cable and
press the key.
Select C10: TAG NO. and press
the key.
OK
ESC
ESC
ESC