Yokogawa EJX440A User Manual
Page 34
IM 01C25T03-01E
5-2
5. PARAMETER SUMMARY
No.
Parameter name
Item
R/W
Content
Applicable model
Upload
data
F
P
L
Default value
D
AUX SET 1
Auxiliary setting data 1
D35
SP POINT
Decimal place of static pressure
W
0 to 4
D36
SP DAMPING
Damping time constant of SP
W
0.00 to 100.00 sec
D37
SP SELECT
H/L select for static pressure
W
HIGH or LOW
D40
TEMP UNIT
Temperature setting unit
W
degC, degF, or K
D50
QUICK RESP
Quick response
W
OFF or ON (enable 0.00 to 0.50 sec at C30)
D55
WRT PROTECT
Write protect indicator
R
NO or YES
D56
WRT ENABLE
Write protect release
W
8 alphanumeric characters
D57
NEW PASSWORD User set password for write protect
W
8 alphanumeric characters
D58
SOFTWR SEAL
Software seal
R
BREAK or KEEP
D60
SELF CHECK
Self-diagnostics
R
See A60
E
AUX SET 2
Auxiliary setting data 2
E10
T. ZERO CMP
Temperature compensation mode
W
OFF or ON
E11
TEMP ZERO
Zero shift compensation
W
Ϫ
99.999 to 99.999%/degC
E30
BI DIRE MODE
Bidirectional mode
W
OFF or ON
E50
DO SELECT
Contact output select
W
INHIBIT, PRES, SP, TEMP, PRES/SP,
PRES/TEMP, SP/TEMP, or PRES/SP/TEMP
E51
DO SIG. TYPE
Signal type select
W
OFF WHEN ALARM or ON WHEN ALARM
E52
D OUTPUT
Contact output
R
OFF or ON
E60
SELF CHECK
Self-diagnostics
R
See A60
G
ALARM SET
Alarm setting
G10
P AL MODE
Alert mode
W
INHIBIT, HI. AL DETECT, LO. AL DETECT,
or HI/LO. AL DETECT
G11
P HI. AL VAL
High side alert value
W
Ϫ
32000 to 32000, unit specified in C20
G12
P LO. AL VAL
Low side alert value
W
Ϫ
32000 to 32000, unit specified in C20
G20
SP AL MODE
Static pressure alert mode
W
INHIBIT, HI. AL DETECT, LO. AL DETECT,
or HI/LO. AL DETECT
G21
SP HI. AL VAL
High side alert value of SP
*
2
W
Ϫ
32000 to 32000, unit specified in D30
G22
SP LO. AL VAL
Low side alert value of SP
W
Ϫ
32000 to 32000, unit specified in D30
G30
T AL MODE
Temperature alert mode
W
INHIBIT, HI. AL DETECT, LO. AL DETECT,
or HI/LO. AL DETECT
G31
T HI. AL VAL
High side alert value of temperature
W
Ϫ
50 to 130
G32
T LO. AL VAL
Low side alert value of temperature
W
Ϫ
50 to 130
G50
AUTO RECOVER Auto-recover from sensor error
W
OFF or ON
G60
SELF CHECK
Self-diagnostics
R
See A60
H AUTO
SET
Automatic
setup
H10
AUTO P LRV
Lower range value auto setup
W
Ϫ
32000 to 32000, unit specified in C20
H11
AUTO P URV
Upper range value auto setup
W
Ϫ
32000 to 32000, unit specified in C20
H20
AUTO SP LRV
SP lower range value auto setup
W
Ϫ
32000 to 32000, unit specified in D30
H21
AUTO SP URV
SP upper range value auto setup
*
2
W
Ϫ
32000 to 32000, unit specified in D30
H60
SELF CHECK
Self-diagnostics
R
See A60
I
DISP SET
Display setting
I10
DISP OUT1
LCD output 1
W
PRES, PRES %, ENGR. PRES, SP, or SP %
I11
DISP OUT2
LCD output 2
W
PRES, PRES %, ENGR. PRES, SP, SP %, or
---
I12
DISP OUT3
LCD output 3
W
See I11
I13
DISP OUT4
LCD output 4
W
See I11
I20
P DISP MODE
% display mode
W
LINEAR or SQUARE ROOT
I21
PRES % RESO
% display resolution
W
NORMAL or HIGH RESOLUTION
I30
ENGR. UNIT
User set engineering unit
W
8 alphanumeric characters
I31
EASY EU SET
Engineering unit select
W
I32 ENGR.
EXP
Exponents
W ---,
ϫ
10,
ϫ
100,
ϫ
1000
I33
ENGR. LRV
User set lower range limit
W
Ϫ
32000 to 32000, unit specified in I30
I34
ENGR. URV
User set upper range limit
W
Ϫ
32000 to 32000, unit specified in I30
I35
ENGR. POINT
Decimal place of user set
W
0 to 4
I40
BAR INDICATR
Bar indicator
W
OFF or ON
I60
SELF CHECK
Self-diagnostics
R
See A60
1
2.00 sec
HIGH
degC
OFF
NO
None
None
KEEP
OFF
0.000%/degC
OFF
INHIBIT
ON WHEN ALARM
OFF
INHIBIT
100.000 kPa
Ϫ
100.000 kPa
INHIBIT
0.00000 MPa
INHIBIT
120 degC
Ϫ
40 degC
ON
As specified
As specified
0.00000 MPa
PRES %
---
---
---
LINEAR
NORMAL
---
0.00
100.00
1
ON
●
-
●
●
●
-
●
●
●
-
●
●
●
●
●
●
●
●
●
●
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
-
●
-
●
-
●
-
●
-
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
●
●
-
●
-
●
-
●
-
●
-
●
●
●
-
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
-
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
-
*
1: R/W: R = Read only, W = Read & Write
*
2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.
*
1