Wa t l o w S e r i e s S D 6 L i m i t w i t h D e v i c e N e t

1 5

Attribute #

Access
Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

152

Get/Set

Alarm 2 Message

BOOLEAN

Display an alarm message
when an alarm is active.

(0) OFF (no message)
(1) ON (default)

153

Get/Set

Upper Display Look

USINT

Select what value appears in
the upper display

(0) - None
(1) - Process
(2) - Limit 1 low
(3) - Limit 1 high (default)
(4) - Limit 2 low
(5) - Limit 2 high
(6) - Alarm 2 Low
(7) - Alarm 2 High

154

Get/Set

Lower Display Look

USINT

Selects what value appears
in the lower display

(0) - None
(1) - Process
(2) - Limit 1 low
(3) - Limit 1 high (default)
(4) - Limit 2 low
(5) - Limit 2 high
(6) - Alarm 2 low
(7) - Alarm 2 high

155

Get

Analog Input Error
Latching

BOOLEAN

Select whether input errors
are latched.

(0) Non-latching (default)
(1) Latching

161

Get/Set

Lockout

USINT

Set the security level for the
user interface.

(0) No Lockout (default)
(1) Programming and
setup page locked
(2) Programming and
setup page locked. Only
limit setpoints accessible
(3) Full lockout

162

Set

Limit Acknowledge for
output 1

BOOLEAN

Clears limit condition for out-
put 1.

(0) No
(1) Yes

163

Set

Limit or Alarm
Acknowledge for output 2

BOOLEAN

Clears alarm or limit condi-
tion for output 2.

(0) No
(1) Yes

165

Get/Set

Analog Input mV Scale
Low

DINT

Sets low scale for millivolt
inputs.

5.00 to 50.00 mV
(default 5.00)

166

Get/Set

Analog Input mV Scale
High

DINT

Sets high scale for millivolt
inputs.

5.00 to 50.00 mV
(default 50.00)

167

Get/Set

Process Milliamp Low
Error

DINT

Sets the low threshold for
input errors when using milli-
amp inputs

1.00 to 10.00 mA
(default 1.00)

170

Get/Set

Process Milliamp High
Error

DINT

Sets the high threshold for
input errors when using milli-
amp inputs

10.00 to 20.00 mA
(default 20.00)