Watlow Series SD6 Limit With Devicenet User Manual
Page 15
Wa t l o w S e r i e s S D 6 L i m i t w i t h D e v i c e N e t
■
1 5
■
Attribute #
Access
Rule
Name
DeviceNet
Data Type
Description of Attribute
Semantics of Values
152
Get/Set
Alarm 2 Message
BOOLEAN
Display an alarm message
when an alarm is active.
(0) OFF (no message)
(1) ON (default)
153
Get/Set
Upper Display Look
USINT
Select what value appears in
the upper display
(0) - None
(1) - Process
(2) - Limit 1 low
(3) - Limit 1 high (default)
(4) - Limit 2 low
(5) - Limit 2 high
(6) - Alarm 2 Low
(7) - Alarm 2 High
154
Get/Set
Lower Display Look
USINT
Selects what value appears
in the lower display
(0) - None
(1) - Process
(2) - Limit 1 low
(3) - Limit 1 high (default)
(4) - Limit 2 low
(5) - Limit 2 high
(6) - Alarm 2 low
(7) - Alarm 2 high
155
Get
Analog Input Error
Latching
BOOLEAN
Select whether input errors
are latched.
(0) Non-latching (default)
(1) Latching
161
Get/Set
Lockout
USINT
Set the security level for the
user interface.
(0) No Lockout (default)
(1) Programming and
setup page locked
(2) Programming and
setup page locked. Only
limit setpoints accessible
(3) Full lockout
162
Set
Limit Acknowledge for
output 1
BOOLEAN
Clears limit condition for out-
put 1.
(0) No
(1) Yes
163
Set
Limit or Alarm
Acknowledge for output 2
BOOLEAN
Clears alarm or limit condi-
tion for output 2.
(0) No
(1) Yes
165
Get/Set
Analog Input mV Scale
Low
DINT
Sets low scale for millivolt
inputs.
5.00 to 50.00 mV
(default 5.00)
166
Get/Set
Analog Input mV Scale
High
DINT
Sets high scale for millivolt
inputs.
5.00 to 50.00 mV
(default 50.00)
167
Get/Set
Process Milliamp Low
Error
DINT
Sets the low threshold for
input errors when using milli-
amp inputs
1.00 to 10.00 mA
(default 1.00)
170
Get/Set
Process Milliamp High
Error
DINT
Sets the high threshold for
input errors when using milli-
amp inputs
10.00 to 20.00 mA
(default 20.00)