Watlow Series SD6 Limit With Devicenet User Manual
Page 14
Wa t l o w S e r i e s S D 6 L i m i t w i t h D e v i c e N e t
■
1 4
■
Attribute #
Access Rule
Name
DeviceNet
Data Type
Description of Attribute
Semantics of Values
121
Get/Set
Set Point High Limit mA
and volts
DINT
Set the high range for the
set point
Set Point Low Limit +
0.001 to 9999, if Input
Type = mA or Volt (default
= 999)
(* 1000)
122
Get/Set
Input Filter
USINT
Select filtering action
(0) OFF (no filtering,
default)
(1) Filter display only
(2) Filter control input only
(3) Filter both
123
Get/Set
Filter Value
UDINT
Set the input filter value, units
in seconds
0.0 to 60.0 (default = 0.0)
seconds
(* 1000)
124
Get/Set
Output 1 Function
USINT
Set the output 1 function
(0) OFF
(2) Limit (default)
125
Get/Set
Output 1 Limit Sides
USINT
Selects output 1 limit active
sides
(0) both (default)
(1) high side
(2) low side
126
Get/Set
Limit 1 hysteresis
DINT
Sets the hysteresis for the
limit on output 1
0.0 to 999.0 (* 1000)
1.0 (default)
136
Get/Set
Output 2 Function
USINT
Set the output 2 function
(0) OFF (default)
(1) Process Alarm
(2) Limit
137
Get/Set
Output 2 Sides
USINT
Selects output 2 limit active
sides
(0) both (default)
(1) high side
(2) low side
138
Get/Set
Output 2 hysteresis
DINT
Sets the hysteresis for the
limit on output 2
0.0 to 999.0 (* 1000)
1.0 (default)
139
Get/Set
Output 2 Logic
BOOLEAN
Output condition in the
alarm state
(0) closed (default)
(1) open
150
Get/Set
Alarm 2 Latching
BOOLEAN
Turn alarm latching on or
off.
(0) OFF (default)
(1) ON
151
Get/Set
Alarm 2 Silencing
BOOLEAN
Turn alarm silencing on or
off.
(0) No silencing (default)
(1) Silencing