Wa t l o w S e r i e s S D 6 L i m i t w i t h D e v i c e N e t

1 4

Attribute #

Access Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

121

Get/Set

Set Point High Limit mA
and volts

DINT

Set the high range for the
set point

Set Point Low Limit +
0.001 to 9999, if Input
Type = mA or Volt (default
= 999)
(* 1000)

122

Get/Set

Input Filter

USINT

Select filtering action

(0) OFF (no filtering,
default)

(1) Filter display only

(2) Filter control input only

(3) Filter both

123

Get/Set

Filter Value

UDINT

Set the input filter value, units
in seconds

0.0 to 60.0 (default = 0.0)
seconds
(* 1000)

124

Get/Set

Output 1 Function

USINT

Set the output 1 function

(0) OFF

(2) Limit (default)

125

Get/Set

Output 1 Limit Sides

USINT

Selects output 1 limit active
sides

(0) both (default)
(1) high side
(2) low side

126

Get/Set

Limit 1 hysteresis

DINT

Sets the hysteresis for the
limit on output 1

0.0 to 999.0 (* 1000)
1.0 (default)

136

Get/Set

Output 2 Function

USINT

Set the output 2 function

(0) OFF (default)
(1) Process Alarm
(2) Limit

137

Get/Set

Output 2 Sides

USINT

Selects output 2 limit active
sides

(0) both (default)
(1) high side
(2) low side

138

Get/Set

Output 2 hysteresis

DINT

Sets the hysteresis for the
limit on output 2

0.0 to 999.0 (* 1000)
1.0 (default)

139

Get/Set

Output 2 Logic

BOOLEAN

Output condition in the
alarm state

(0) closed (default)
(1) open

150

Get/Set

Alarm 2 Latching

BOOLEAN

Turn alarm latching on or
off.

(0) OFF (default)
(1) ON

151

Get/Set

Alarm 2 Silencing

BOOLEAN

Turn alarm silencing on or
off.

(0) No silencing (default)
(1) Silencing