Data Communications with the Watlow Series 988 Family

Temperature/process Controller Prompt Table

986, 987,

988

, 989

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

6.10

Command Summary Series 986-989, Chapter 6

PID2

PID Set Crossover

? PID2

0 = Process

101

Source Selection

= PID2 data.2

1 = Set point
2 = None
Default: 0

PRC1

Process Range

? PRC1

0 = 4-20mA

68

Output 1

= PRC1 data.2

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

PRC2

Process Range

? PRC2

0 = 4-20mA

71

Output 2

= PRC2 data.2

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

PRC3

Process Range

? PRC3

0 = 4-20mA

91

Output 3

= PRC3 data.2

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

PROC Process Value for

? PROC

RL1 to RH1

102

PID A <-> B Switch

= PROC data.2

Default: per IN1 and hardware

PWR

Percent Power

? PWR

-100% to 100%

6

Present Output

n/a

RA1A

Rate Output 1

? RA1A

0.00 to 9.99 minutes

23

PID Set A

= RA1A data.2

Default: 0.00

RA1B

Rate Output 1

? RA1B

0.00 to 9.99 minutes

36

PID Set B

= RA1B data.2

Default: 0.00

RA2A

Rate Output 2

? RA2A

0.00 to 9.99 minutes

29

PID Set A

= RA2A data.2

Default: 0.00

RA2B

Rate Output 2

? RA2B

0.00 to 9.99 minutes

42

PID Set B

= RA2B data.2

Default: 0.00

RE1A

Reset Output 1

? RE1A

if ALGO = 0, 1, or 3, then

22

PID Set A

= RE1A data.2

0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%

RE1B

Reset Output 1

? RE1B

if ALGO = 0, 1, or 3, then

35

PID Set B

= RE1B data.2

0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%

RE2A

Reset Output 2

? RE2A

if ALGO = 0, 1, or 3, then

28

PID Set A

= RE2A data.2

0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%

RE2B

Reset Output 2

? RE2B

if ALGO = 0, 1, or 3, then

41

PID Set B

= RE2B data.2

0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%

RH1

Range High

? RH1

min. IN1 range to to max. IN1 range

50

Input 1

= RH1 data.2

Default: Sensor high range

RH2

Range High

? RH2

min. IN2 range to to max. IN2 range

58

Input 2

= RH2 data.2

Default: Sensor high range

Table 6.10 -

PID2 to RH2

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)