Temperature/process controller prompt table, Table 6.10, Pid2 to rh2 – Watlow Series 988 Family User Manual
Page 54

Data Communications with the Watlow Series 988 Family
Temperature/process Controller Prompt Table
986, 987,
988
, 989
Name
Description
Read (?) and/or Write (=) Syntax
Range
data.1
data.2
Modbus
address
6.10
Command Summary Series 986-989, Chapter 6
PID2
PID Set Crossover
?
0 = Process
101
Source Selection
=
1 = Set point
2 = None
Default: 0
PRC1
Process Range
?
0 = 4-20mA
68
Output 1
=
1 = 0-20mA
2 = 0-5V
Î
(dc)
3 = 1-5V
Î
(dc)
4 = 0-10V
Î
(dc)
Default: 0
PRC2
Process Range
?
0 = 4-20mA
71
Output 2
=
1 = 0-20mA
2 = 0-5V
Î
(dc)
3 = 1-5V
Î
(dc)
4 = 0-10V
Î
(dc)
Default: 0
PRC3
Process Range
?
0 = 4-20mA
91
Output 3
=
1 = 0-20mA
2 = 0-5V
Î
(dc)
3 = 1-5V
Î
(dc)
4 = 0-10V
Î
(dc)
Default: 0
PROC Process Value for
?
RL1 to RH1
102
PID A <-> B Switch
=
Default: per IN1 and hardware
PWR
Percent Power
?
-100% to 100%
6
Present Output
n/a
RA1A
Rate Output 1
?
0.00 to 9.99 minutes
23
PID Set A
=
Default: 0.00
RA1B
Rate Output 1
?
0.00 to 9.99 minutes
36
PID Set B
=
Default: 0.00
RA2A
Rate Output 2
?
0.00 to 9.99 minutes
29
PID Set A
=
Default: 0.00
RA2B
Rate Output 2
?
0.00 to 9.99 minutes
42
PID Set B
=
Default: 0.00
RE1A
Reset Output 1
?
if ALGO = 0, 1, or 3, then
22
PID Set A
=
0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%
RE1B
Reset Output 1
?
if ALGO = 0, 1, or 3, then
35
PID Set B
=
0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%
RE2A
Reset Output 2
?
if ALGO = 0, 1, or 3, then
28
PID Set A
=
0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%
RE2B
Reset Output 2
?
if ALGO = 0, 1, or 3, then
41
PID Set B
=
0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%
RH1
Range High
?
min. IN1 range to to max. IN1 range
50
Input 1
=
Default: Sensor high range
RH2
Range High
?
min. IN2 range to to max. IN2 range
58
Input 2
=
Default: Sensor high range
Table 6.10 -
PID2 to RH2
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)