Temperature/process controller prompt table, Table 6.9, Ot3 to pidb – Watlow Series 988 Family User Manual

Page 53

background image

Temperature/process Controller Prompt Table

986, 987,

988

, 989

Data Communications with the Watlow Series 988 Family

6.9

Command Summary Series 986-989, Chapter 6

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

OT3

Output 3 Action

? OT3

0 = None

78

= OT3 data.2

1 = Alarm 3
2 = Alarm 3 reverse acting

OTPT

Lockout Output

? OTPT

0 = No lockout

117

Menu

= OTPT data.2

1 = Read only
2 = No read or write
Default: 0

OTY1

Output 1 Hardware

? OTY1

0 = None

132

1 = SSR 0.5A

OTY2

Output 2 Hardware

? OTY2

2 = SSR 0.5A with suppression

133

6 = Switched dc

OTY3

Output 3 Hardware

? OTY3

8 = Relay 5A Form C

134

9 = Relay 5A Form C with suppr.

OTY4

Output 4 Hardware

? OTY4

10 = Relay 5A Form A/B

135

11 = Relay 5A Form A/B with suppr.
13 = Process output
14 = Voltage retransmit
15 = Current retransmit
16 = Power supply
17 = Comms EIA-232
18 = Comms EIA -485 / EIA-422
19 = Comms EIA-485 / EIA-232

PB1A

Proportional Band

? PB1A

if DFL = 0, then 0 to 9999

21

Output 1 PID Set A

= PB1A data.2

if DFL = 1, then 0.0 to 99.9% of span
Default: 25

°

F, 14

°

C, 25 units or 3.0%

PB1B

Proportional Band

? PB1B

if DFL = 0, then 0 to 9999

34

Output 1 PID Set B

= PB1B data.2

if DFL = 1, then 0.0 to 99.9% of span
Default: 25

°

F, 14

°

C, 25 units or 3.0%

PB2A

Proportional Band

? PB2A

if DFL = 0, then 0 to 9999

27

Output 2 PID Set A

= PB2A data.2

if DFL = 1, then 0.0 to 99.9% of span
Default: 25

°

F, 14

°

C, 25 units or 3.0%

PB2B

Proportional Band

? PB2B

if DFL = 0, then 0 to 9999

40

Output 2 PID Set B

= PB2B data.2

if DFL = 1, then 0.0 to 99.9% of span
Default: 25

°

F, 14

°

C, 25 units or 3.0%

PIDA

Lockout PID Set A

? PIDA

0 = No lockout

114

Menu

= PIDA data.2

1 = Read only
2 = No read or write
Default: 0

PIDB

Lockout PID Set B

? PIDB

0 = No lockout

115

Menu

= PIDB data.2

1 = Read only
2 = No read or write
Default: 0

Table 6.9 -

OT3 to PIDB

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)