beautypg.com

Temperature/process controller prompt table, Table 6.6, Ftr1 to in1 – Watlow Series 988 Family User Manual

Page 50

background image

Data Communications with the Watlow Series 988 Family

Temperature/process Controller Prompt Table

986, 987,

988

, 989

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

6.6

Command Summary Series 986-989, Chapter 6

FTR1

Process Input 1

? FTR1

-60 to 60 seconds

53

Filter Time Constant = FTR1 data.2

Default: 0

FTR2

Process Input 2

? FTR2

-60 to 60 seconds

63

Filter Time Constant = FTR2 data.2

Default: 0

GLBL

Lockout

? GLBL

0 = No lockout

118

Global Menu

= GLBL data.2

1 = Read only
2 = No read or write
Default: 0

HIP

High Power Limit

? HIP

LOP (%) to 100%

108

= HIP data.2

Default: 100 (Heat / cool)
Default: 0 (Cool only)

HUNT Slidewire

? HUNT

0.1% to 100.0%

65

Deadband %

= HUNT data.2

Default: 1.0%

HYS1

Output 1 Hysteresis

? HYS1

0

°

F to 999

°

F

69

= HYS1 data.2

0

°

C to 555

°

C

0 units to 999 units
Default: 3

°

F, 2

°

C, or 3 units

HYS2

Output 2 Hysteresis

? HYS2

0

°

F to 999

°

F

72

= HYS2 data.2

0

°

C to 555

°

C

0 units to 999 units
Default: 3

°

F, 2

°

C, or 3 units

HYS3

Output 3 Hysteresis

? HYS3

0

°

F to 999

°

F

81

= HYS3 data.2

0

°

C to 555

°

C

0 units to 999 units
Default: 3

°

F, 2

°

C, or 3 units

IDSP

Idle Set Point

? IDSP

RL1 to RH1

9

= IDSP data.2

IN1

Input 1 Type

? IN1

1 = J t/c; 32 to 1500

°

F/0 to 816

°

C

47

= IN1 data.2

2 = K t/c; -328 to 2500

°

F/-200 to 1371

°

C

(Caution: Writing to

3 = T t/c; -328 to 750

°

F/-200 to 399

°

C

IN1 resets most

4 = N t/c; 32 to 2372

°

F/0 to 1300

°

C

prompts to their de-

5 = E t/c; -328 to 1470

°

F/-200 to 799

°

C

fault state.)

6 = C t/c (W3); 32 to 4200

°

F 0 to 2316

°

C

7 = D t/c (W5); 32 to 4200

°

F/0 to 2316

°

C

8 = Pt 2; 32 to 2543

°

F/0 to 1395

°

C

10 = R t/c; 32 to 3200

°

F/0 to 1760

°

C

11 = S t/c; 32 to 3200

°

F/0 to 1760

°

C

12 = B t/c; 1598 to 3300

°

F/870 to 1816

°

C

14 = 1

°

RTD (DIN); -328 to 1472

°

F/

-200 to 800

°

C

15 = 0.1

°

RTD (DIN); -99.9 to 999.9

°

F/

-99.9 to 700.0

°

C

17 = 4-20mA; -999 to 9999 units
18 = 0-20mA; -999 to 9999 units
19 = 0-5V

Î

(dc); -999 to 9999 units

20 = 1-5V

Î

(dc); -999 to 9999 units

21 = 0-10V

Î

(dc); -999 to 9999 units

23 = 0-50mV

Î

(dc); -999 to 9999 units

24 = 0-100mV

Î

(dc); -999 to 9999 units

34 = 0-50mV

Î

(dc); -999 to 9999 units

Table 6.6 -

FTR1 to IN1

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.

NOTE:
(RTD setting)
For JIS curve, go
to rtd1 prompt
after selecting In1.