Ramping controller prompt table, Table 5.10, Ptyp to soft – Watlow Series 988 Family User Manual
Page 38

Name
Description
Read (?) and/or Write (=) Syntax
Range
data.1
data.2
Modbus
Address
Ramping Controller Prompt Table
981,
982,
983, 984
Data Communications with the Watlow Series 988 Family
Command Summary Series 981-984, Chapter 5
5.10
PTYP
Program Type;
?
0 = Time-based; hour:min:sec
1208
Time-based, or
=
1 = Ramp rate-based; °/minute
Ramp rate-based
Default: 0
PWR
Percent Power
?
-100% to 100%
103
Present Output
Default: n/a
RA1
Rate Output 1
?
0.00 to 9.99 minutes
504
=
Default: 0.00
RA2
Rate Output 2
?
0.00 to 9.99 minutes
514
=
Default: 0.00
RE1
Reset Output 1
?
0.00 to 9.99 repeats/min.
502
=
Default: 0.10 repeats/min.
RE2
Reset Output 2
?
0.00 to 9.99 repeats/min.
512
=
Default: 0.10 repeats/min.
RESU Resume a Program
=
1 = Resumes current file# and step#
1209
RH1
Range High
?
min. IN1 range to max. IN1 range
603
Input 1
=
Default: sensor high range
RH2
Range High
?
min. IN2 range to max. IN2 range
613
Input 2
=
Default: sensor high range
RHS
Run/Hold Status
?
0 = Hold
200
1 = Run
2 = Pre-run
RL1
Range Low
?
min. IN1 range to max. IN1 range
602
Input 1
=
Default: sensor low range
RL2
Range Low
?
min. IN2 range to max. IN2 range
612
Input 2
=
Default: sensor low range
RTD1
RTD Calibration
?
0 = JIS
609
Curve Input 1
=
1 = DIN
Default: 1
SIL2
Alarm 2 Silence
?
0 = off/disabled
722
=
1 = on/enabled
Default: 0
SIL3
Alarm 3 Silence
?
0 = off/disabled
739
=
1 = on/enabled
Default: 0
SRNB Serial Number
?
xxxx =
2
Bottom Display
0000 to 9999
Read the six-digit
unit serial number
in two segments,
SNxx and xxxx,
i.e., upper and lower
front panel displays.
SRNT
Serial Number
?
SNxx =
1
Top Display
00 to 99
SOFT
Software Revision
?
0 = Rev A
8 = Rev I
4
1 = Rev B
9 = Rev J
2 = Rev C
10 = Rev K
3 = Rev D
11 = Rev L
4 = Rev E
12 = Rev M
5 = Rev F
13 = Rev N
6 = Rev G
etc..........
7 = Rev H
Table 5.10 -
PTYP to SOFT
ç
CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.
(This does not
apply to Modbus
Protocol.)