Temperature/process controller prompt table, Table 6.4, Ct1a to diag – Watlow Series 988 Family User Manual

Page 48

background image

Data Communications with the Watlow Series 988 Family

Temperature/process Controller Prompt Table

986, 987,

988

, 989

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

6.4

Command Summary Series 986-989, Chapter 6

CT1A

Cycle Time

? CT1A

S.S. relay or open col:

26

Output 1 PID Set A

= CT1A data.2

0.0 = Burst firing, or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

CT1B

Cycle Time

? CT1B

S.S. relay or open col:

39

Output 1 PID Set B

= CT1B data.2

0.0 = Burst firing (brSt), or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

CT2A

Cycle Time

? CT2A

S.S. relay or open col:

32

Output 2 PID Set A

= CT2A data.2

0.0 = Burst firing (brSt), or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

CT2B

Cycle Time

? CT2B

S.S. relay or open col:

45

Output 2 PID Set B

= CT2B data.2

0.0 = Burst firing (brSt), or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

DATE

Factory

? DATE

xxyy

122

Test Date

xx = week
yy = year

DBA

Deadband

? DBA

-999

°

F to 999

°

F

33

PID Set A

= DBA data.2

-555

°

C to 555

°

C

-999 units to 999 units
Default: 0

°

F, 0

°

C, or 0 units

DBB

Deadband

? DBB

-999

°

F to 999

°

F

46

PID Set B

= DBB data.2

-555

°

C to 555

°

C

-999 units to 999 units
Default: 0

°

F, 0

°

C, or 0 units

DE1A

Derivative

? DE1A

0.00 to 9.99 minutes

25

Output 1 PID Set A

= DE1A data.2

Default: 0.00

DE2A

Derivative

? DE2A

0.00 to 9.99 minutes

31

Output 2 PID Set A

= DE2A data.2

Default: 0.00

DE1B

Derivative

? DE1B

0.00 to 9.99 minutes

38

Output 1 PID Set B

= DE1B data.2

Default: 0.00

DE2B

Derivative

? DE2B

0.00 to 9.99 minutes

44

Output 2 PID Set B

= DE2B data.2

Default: 0.00

DEC1

Decimal Point

? DEC1

0 = Decimal point 0

48

Process Input 1

= DEC1 data.2

1 = Decimal point 0.0
2 = Decimal point 0.00
3 = Decimal point 0.000
Default: 0

DEC2

Decimal Point

? DEC2

0 = Decimal point 0

56

Process Input 2

= DEC2 data.2

1 = Decimal point 0.0
2 = Decimal point 0.00
3 = Decimal point 0.000
Default: 0

DEV

Process Deviation

? DEV

Difference between SP1 and C1

5

Display Loop (IN 1)

DFL

Default Unit Type

? DFL

0 = US units

140

= DFL data.2

1 = Standard International units

DIAG

Lockout

? DIAG

0 = No lockout

120

Diagnostics Menu

= DIAG data.2

1 = Read only
2 = No read or write
Default: 0

Table 6.4 -

CT1A to DIAG

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)