Entering the setup menu, Setup menu, Operation menu – Watlow Series 965 User Manual

Page 42

background image

75

Pb1

rE1/It1

rA1/dE1

Ct1

ALO

AHI

CAL

AUt

( )

( )

( )

( )

( )

( )

( )

( )

Pb2

( )

rE2/It2

rA2/dE2

Ct2

( )

( )

( )

Proportional band 1

Reset 1/Integral 1

Cycle time 1

Proportional band 2

Reset 2/Integral 2

Rate 2/Deviation 2

Cycle time 2

Rate 1/Deviation 1

Control Set Point

Alarm low

Alarm high

Calibration offset

Auto-tune

Parameters

Value

Range

Factory Default

Appears If:

LOC

0 through 4

0

In

J, K (appears as H), t, n, S, rtd, rt.d, 0-5, 420

J

DIP switch selectable

dEC

0, 0.0, 0.00

0

In = 0-5 or 420

C_F

C or F

C

dFL = SI or In = T/C or RTD

F

dFL = US or In = T/C or RTD

rL

rL to rH

Input dependent

rH

rH to rL

Input dependent

Ot1

ht or CL

ht

HSC

1 to 99, 0.1 - 9.9, 0.01 - 0.99

3, 0.3, 0.03

°

F

Ot2

Con = Control

Con

PrA = Process alarm
Pr = Process with no alarm message
dEA = Deviation alarm
dE = Deviation with no alarm message
no = None

HSA

1 to 9999, 0.1 - 999.9, 0.01 - 99.99

3, 0.3, 0.03

°

F

Ot2

Con or no

LAt

LAt or nLA

nLA

Ot2

Con or no

SIL

On or OFF

OFF

Ot2 = dEA or dE

rtd

JIS or din

din

In = rtd or rt.d

r P

Str = Ramping on power up

OFF

on = Ramping to set point at all times
OFF = None

rt

0 to 9999

100

°

/hr

rP

OFF

P L

0 to 100

100

dSP

nor = Normal

nor

SEt = Set Point (lower display only)
Pro = Process (upper display only)

Entering the Setup Menu

The Setup Menu displays the parameters that configure the Series 965's features to your applicaton.

Enter the Setup menu by pressing the Up-arrow/Down-arrow keys simultaneously for 3 seconds. The lower
display shows the LOC parameter, and the upper display shows its current level. All keys are inactive until you
release both keys. You can reach the LOC parameter from anywhere.

You will not see all parameters in these menus depending on your unit's configuration and model number.

Do not enter any values here; make photocopies instead.

Setup Menu

Parameters

Value

Range

Factory Default

Appears If:

Pb1

0 to 999

°

F/0 to 555

°

C/0 to 999 Units

25

°

F

dFL = US

0 to 99.9

°

F/ 0 to 55.5

°

C/0 TO 99.9 UNITS

2.5

°

F

0.0 to 999.9% of span

3% / .3%

dFL = SI

0 = ON/OFF control, HSC = Switching diff.

rE1

0.00 to 9.99 repeats/minute / 0.00 = No reset

0.00 repeats/minute

Pb1

0 or dFL = US

It1

00.0 to 99.9 minutes/repeat / 0.00 = No integral

00.0 minutes/repeat

Pb1

0 or dFL = SI

rA1

0.00 to 9.99 minutes / 0.00 = No rate

0.00 minutes

Pb1

0 or dFL = US

dE1

0.00 to 9.99 minutes / 0.00 = No derivativew

0.00 minutes

Pb1

0 or dFL is SI

Ct1

0.1 to 999.9 seconds

5.0 seconds

Pb1

0 or Output 1

420

Pb2

1 to 999

°

F/0 to 555

°

C/0 to 999 Units

25

°

F

dFL = US

1 to 99.9

°

F/ 0 to 55.5

°

C/0 to 99.9 Units

2.5

°

F

0.1 to 999.9% of span

3% / .3%

dFL = SI, Ot2 = Con, Pb1

0

rE2

0.00 to 9.99 repeats/minute / 0.00 = No reset

0.00 repeats/minute

dFL = US, Ot2 = Con, Pb1

0

It2

00.0 to 99.9 minutes/repeat / 0.00 = No integral

00.0 minutes/repeat

dFL = SI, Ot2 = Con, Pb1

0

rA2

0.00 to 9.99 minutes / 0.00 = No rate

0.00 minutes

dFL = US, Ot2 = Con, Pb1

0

dE2

0.00 to 9.99 minutes / 0.00 = No derivative

0.00 minutes

dFL = SI, Ot2 = Con, Pb1

0

Ct2

0.1 to 999.9 seconds

5.0 seconds

Ot2 = Con, Pb1

0

ALO

-999

°

to 0

-999

°

Ot2 = dE or dEA

rL to AHI

rL

Ot2 = Pr or PrA

AHI

0 to 999

°

999

°

Ot2 = dE or dEA

ALO to rH

rH

Ot2 = Pr or PrA

CAL

±

18

°

F/

±

10

°

C/

±

18 Units

0

AUt

0 = off, 1 = slow, 2 = medium, 3 = fast

0

Do not enter any values here; make photocopies instead.

Operation Menu

(

)

(

)

Rate 1/Derivative 1

Rate 2/Derivative 2

LOC

In

C _ F

rL

rH

Ot 1

HSC

Ot2

LAt

SIL

rtd

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

75

rP

rt

PL

( )

( )

( )

dEC

( )

HSA

( )

User lock out

Input type

Celcius__Fahrenheit

Range low

Range high

Output 1

Control hysteresis

Output 2

Latching for alarm

Silence alarm

RTD calibration curve

Ramp func tion

Ramp rate

Power limiting

Decimal place

Output 2 hysteresis

dSP

( )

Display