Entering the setup menu, Setup menu, Operation menu – Watlow Series 965 User Manual
Page 42
75
Pb1
rE1/It1
rA1/dE1
Ct1
ALO
AHI
CAL
AUt
( )
( )
( )
( )
( )
( )
( )
( )
Pb2
( )
rE2/It2
rA2/dE2
Ct2
( )
( )
( )
Proportional band 1
Reset 1/Integral 1
Cycle time 1
Proportional band 2
Reset 2/Integral 2
Rate 2/Deviation 2
Cycle time 2
Rate 1/Deviation 1
Control Set Point
Alarm low
Alarm high
Calibration offset
Auto-tune
Parameters
Value
Range
Factory Default
Appears If:
LOC
0 through 4
0
In
J, K (appears as H), t, n, S, rtd, rt.d, 0-5, 420
J
DIP switch selectable
dEC
0, 0.0, 0.00
0
In = 0-5 or 420
C_F
C or F
C
dFL = SI or In = T/C or RTD
F
dFL = US or In = T/C or RTD
rL
rL to rH
Input dependent
rH
rH to rL
Input dependent
Ot1
ht or CL
ht
HSC
1 to 99, 0.1 - 9.9, 0.01 - 0.99
3, 0.3, 0.03
°
F
Ot2
Con = Control
Con
PrA = Process alarm
Pr = Process with no alarm message
dEA = Deviation alarm
dE = Deviation with no alarm message
no = None
HSA
1 to 9999, 0.1 - 999.9, 0.01 - 99.99
3, 0.3, 0.03
°
F
Ot2
≠
Con or no
LAt
LAt or nLA
nLA
Ot2
≠
Con or no
SIL
On or OFF
OFF
Ot2 = dEA or dE
rtd
JIS or din
din
In = rtd or rt.d
r P
Str = Ramping on power up
OFF
on = Ramping to set point at all times
OFF = None
rt
0 to 9999
100
°
/hr
rP
≠
OFF
P L
0 to 100
100
dSP
nor = Normal
nor
SEt = Set Point (lower display only)
Pro = Process (upper display only)
Entering the Setup Menu
The Setup Menu displays the parameters that configure the Series 965's features to your applicaton.
Enter the Setup menu by pressing the Up-arrow/Down-arrow keys simultaneously for 3 seconds. The lower
display shows the LOC parameter, and the upper display shows its current level. All keys are inactive until you
release both keys. You can reach the LOC parameter from anywhere.
You will not see all parameters in these menus depending on your unit's configuration and model number.
Do not enter any values here; make photocopies instead.
Setup Menu
Parameters
Value
Range
Factory Default
Appears If:
Pb1
0 to 999
°
F/0 to 555
°
C/0 to 999 Units
25
°
F
dFL = US
0 to 99.9
°
F/ 0 to 55.5
°
C/0 TO 99.9 UNITS
2.5
°
F
0.0 to 999.9% of span
3% / .3%
dFL = SI
0 = ON/OFF control, HSC = Switching diff.
rE1
0.00 to 9.99 repeats/minute / 0.00 = No reset
0.00 repeats/minute
Pb1
≠
0 or dFL = US
It1
00.0 to 99.9 minutes/repeat / 0.00 = No integral
00.0 minutes/repeat
Pb1
≠
0 or dFL = SI
rA1
0.00 to 9.99 minutes / 0.00 = No rate
0.00 minutes
Pb1
≠
0 or dFL = US
dE1
0.00 to 9.99 minutes / 0.00 = No derivativew
0.00 minutes
Pb1
≠
0 or dFL is SI
Ct1
0.1 to 999.9 seconds
5.0 seconds
Pb1
≠
0 or Output 1
≠
420
Pb2
1 to 999
°
F/0 to 555
°
C/0 to 999 Units
25
°
F
dFL = US
1 to 99.9
°
F/ 0 to 55.5
°
C/0 to 99.9 Units
2.5
°
F
0.1 to 999.9% of span
3% / .3%
dFL = SI, Ot2 = Con, Pb1
≠
0
rE2
0.00 to 9.99 repeats/minute / 0.00 = No reset
0.00 repeats/minute
dFL = US, Ot2 = Con, Pb1
≠
0
It2
00.0 to 99.9 minutes/repeat / 0.00 = No integral
00.0 minutes/repeat
dFL = SI, Ot2 = Con, Pb1
≠
0
rA2
0.00 to 9.99 minutes / 0.00 = No rate
0.00 minutes
dFL = US, Ot2 = Con, Pb1
≠
0
dE2
0.00 to 9.99 minutes / 0.00 = No derivative
0.00 minutes
dFL = SI, Ot2 = Con, Pb1
≠
0
Ct2
0.1 to 999.9 seconds
5.0 seconds
Ot2 = Con, Pb1
≠
0
ALO
-999
°
to 0
-999
°
Ot2 = dE or dEA
rL to AHI
rL
Ot2 = Pr or PrA
AHI
0 to 999
°
999
°
Ot2 = dE or dEA
ALO to rH
rH
Ot2 = Pr or PrA
CAL
±
18
°
F/
±
10
°
C/
±
18 Units
0
AUt
0 = off, 1 = slow, 2 = medium, 3 = fast
0
Do not enter any values here; make photocopies instead.
Operation Menu
(
)
(
)
Rate 1/Derivative 1
Rate 2/Derivative 2
LOC
In
C _ F
rL
rH
Ot 1
HSC
Ot2
LAt
SIL
rtd
( )
( )
( )
( )
( )
( )
( )
( )
( )
( )
( )
75
rP
rt
PL
( )
( )
( )
dEC
( )
HSA
( )
User lock out
Input type
Celcius__Fahrenheit
Range low
Range high
Output 1
Control hysteresis
Output 2
Latching for alarm
Silence alarm
RTD calibration curve
Ramp func tion
Ramp rate
Power limiting
Decimal place
Output 2 hysteresis
dSP
( )
Display