Operation menu, 20 operation menu table, 20 operation menu prompts/description – Watlow Series 965 User Manual
Page 20: Operation
Setup, Chapter 4
20
WATLOW Series 965 User's Manual
Alarm Low: Represents the low process alarm or low deviation alarm. This
parameter will not appear if Ot 2 = no or Con.
If Ot2 = dEA or dE:
Range: -999 to 0
Default: -999
If Ot2 = PrA or Pr:
Range: rL to AHI
Default: rL
Alarm High: Represents the high process alarm or high deviation alarm. This
parameter will not appear if Ot2 = no or Con.
If Ot2 = dEA or dE:
Range: 0 to 999
Default: 999
If Ot2 = PrA or Pr:
Range: ALO to rH
Default: rH
Calibration Offset: Adds or subtracts degrees from the input signal.
Range: -180
°
F to 180
°
F/-100
°
C to 100
°
C/-180 units to 180 units; or
-18.0
°
F to 18.0
°
F/-10.0
°
C to 10.0
°
C
Default: 0
Auto-Tune: Initiates auto-tune.
Range: 0 = off, 1 = slow, 2 = medium, 3 = fast
Default: 0
Operation
Table 3 -
Operation Menu
Prompts and
Descriptions.
ALO
Operation Parameters
Value
Range
Factory Default
Pb1
If dFL = US:
0 - 999
°
F/0 - 555
°
C/0 - 999 Units
25
°
F
0 - 99.9
°
F/0 - 55.5
°
C/0 - 99.9 Units
2.5
°
F
0=ON/OFF control. HSC =switch diff.
If dFL = SI:
0.0 to 999.9% of span
3%
rE1
0.00 to 9.99 repeats/minute
0.00 repeats/minute
0.00 = No Reset. Won't appear if Pb1 = 0
or dFL = SI.
It1
0.0 - 99.9 minutes/rpt. 0.00 = No Integral.
00.0 minutes/repeat
Won't appear if Pb1 = 0 or dFL = US.
rA1
0.00 to 9.99 minutes
0.00 minutes
0.00 = No Rate. Will not appear if Pb1 = 0
or dFL = SI.
dE1
0.00 - 9.99 minutes. 0.00 = No Derivative.
0.00 minutes
Won't appear if Pb 1 = 0 or dFL = US.
Ct1
0.1 to 999.9
5.0 seconds
Won't appear if Pb1 = 0, or 4-20mA.
Pb2
Same as Pb1. Pb2 lower limit = 1, 0.1, 0.01
rE2
Same range as rE1.
It2
Same range as It1.
rA2
Same range as rA1.
dE2
Same range as dE1.
Ct2
Same range as Ct1.
ALO -
Deviation dE
-999 to 0
-999
Process Pr
rL to AHI
rL
Will not appear if Ot2 = no or Con.
AHI -
Deviation dE
0 to 999
999
Process Pr
ALO to rH
rH
Will not appear if Ot2 = no or Con.
CAL
±
18
°
F/
±
10
°
C/
±
18 Units
0
AUt
0-3
0
Operation Menu
Use this page as a master copy for your Series 965 Operation Parameters.
Do not enter any values here; make photocopies instead.
AHI
AUt