beautypg.com

Operation menu, 20 operation menu table, 20 operation menu prompts/description – Watlow Series 965 User Manual

Page 20: Operation

background image

Setup, Chapter 4

20

WATLOW Series 965 User's Manual

Alarm Low: Represents the low process alarm or low deviation alarm. This
parameter will not appear if Ot 2 = no or Con.
If Ot2 = dEA or dE:

Range: -999 to 0

Default: -999

If Ot2 = PrA or Pr:

Range: rL to AHI

Default: rL

Alarm High: Represents the high process alarm or high deviation alarm. This
parameter will not appear if Ot2 = no or Con.
If Ot2 = dEA or dE:

Range: 0 to 999

Default: 999

If Ot2 = PrA or Pr:

Range: ALO to rH

Default: rH

Calibration Offset: Adds or subtracts degrees from the input signal.
Range: -180

°

F to 180

°

F/-100

°

C to 100

°

C/-180 units to 180 units; or

-18.0

°

F to 18.0

°

F/-10.0

°

C to 10.0

°

C

Default: 0

Auto-Tune: Initiates auto-tune.
Range: 0 = off, 1 = slow, 2 = medium, 3 = fast

Default: 0

Operation

Table 3 -
Operation Menu
Prompts and
Descriptions.

ALO

Operation Parameters

Value

Range

Factory Default

Pb1

If dFL = US:
0 - 999

°

F/0 - 555

°

C/0 - 999 Units

25

°

F

0 - 99.9

°

F/0 - 55.5

°

C/0 - 99.9 Units

2.5

°

F

0=ON/OFF control. HSC =switch diff.
If dFL = SI:
0.0 to 999.9% of span

3%

rE1

0.00 to 9.99 repeats/minute

0.00 repeats/minute

0.00 = No Reset. Won't appear if Pb1 = 0
or dFL = SI.

It1

0.0 - 99.9 minutes/rpt. 0.00 = No Integral.

00.0 minutes/repeat

Won't appear if Pb1 = 0 or dFL = US.

rA1

0.00 to 9.99 minutes

0.00 minutes

0.00 = No Rate. Will not appear if Pb1 = 0
or dFL = SI.

dE1

0.00 - 9.99 minutes. 0.00 = No Derivative.

0.00 minutes

Won't appear if Pb 1 = 0 or dFL = US.

Ct1

0.1 to 999.9

5.0 seconds

Won't appear if Pb1 = 0, or 4-20mA.

Pb2

Same as Pb1. Pb2 lower limit = 1, 0.1, 0.01

rE2

Same range as rE1.

It2

Same range as It1.

rA2

Same range as rA1.

dE2

Same range as dE1.

Ct2

Same range as Ct1.

ALO -

Deviation dE

-999 to 0

-999

Process Pr

rL to AHI

rL

Will not appear if Ot2 = no or Con.

AHI -

Deviation dE

0 to 999

999

Process Pr

ALO to rH

rH

Will not appear if Ot2 = no or Con.

CAL

±

18

°

F/

±

10

°

C/

±

18 Units

0

AUt

0-3

0

Operation Menu

Use this page as a master copy for your Series 965 Operation Parameters.
Do not enter any values here; make photocopies instead.

AHI

AUt

CAL