Output 1 wiring, Switched dc output, Process, 4-20ma – Watlow Series 965 User Manual
Page 10: 10 output 1 wiring, 10 switched dc output wiring, 10 5a mechanical relay wiring, 10 4-20ma process wiring, Switched dc output model # 965a - 3
Install and Wire, Chapter 2
10
WATLOW Series 965 User's Manual
Switched DC Output
Model # 965A - 3
C
- 00
.
Output 1 Wiring
Figure 12 -
Switched dc Output
Wiring
Figure 15 -
0.5 Amp Solid-state
Relay Without
Contact Suppression
Wiring
Mechanical Relay Without Contact Suppression, Form C, 5 Amp
Model # 965A - 3 D - 00
.
External
Load
10
9
-
+
Figure 14 -
4-20mA Process
Wiring
Solid-state Relay Without Contact Suppression, 0.5 Amp
Model # 965A - 3 K - 00
.
External
Load
10
9
-
+
Maximum load
resistance:
800
Ω
Process, 4-20mA
Model # 965A - 3 F - 00
.
NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay, switched dc or
solid-state relay
output options
requires using an
R.C. suppressor.
Watlow carries the
R.C suppressor
Quencharc brand
name, which is a
trademark of ITW
Pakron. Watlow Part
No. 0804-0147-0000.
Figure 13 -
5 Amp Mechanical
Relay Wiring
NOTE:
When an external
device with a non-
isolated circuit
common is connected
to the 4-20mA or
Switched dc output,
you must use an
isolated or un-
grounded thermo-
couple.
External
Load
1 0
9
N O
C O M
8
N C
Fuse
L 1
L 2
Customer Supplied
Quencharc
10
unregulated
V+
V—
9
Internal Circuitry
External
Load
1 0
S S 1
S S 1
8
Fuse
L 1
L 2
Custommer Supplied
Quencharc