beautypg.com

Specifications – Watlow EZ-ZONE PM Express User Manual

Page 30

background image

EZ-ZONE PM Express (PID)

• 30 •

Specifications

Specifications

Line Voltage/Power

• All voltage levels represent minimums and maximums

• 85 to 264V~(ac), 47 to 63Hz

• 20 to 28VÅ(ac), +10/-15 percent; 50/60Hz, ±5 percent

• 12 to 40VÎ(dc)

• 10VA maximum power consumption (PM3 and PM6)

• 14VA maximum power consumption (PM4, 8 and 9)

• Data retention upon power failure via nonvolatile memory

• Compliant with SEMI F47-0200, Figure R1-1 voltage sag requirements @ 24VÅ(ac) or higher
Environment

• -18 to 65°C (0 to 149°F) operating temperature

• -40 to 85°C (-40 to 185°F) storage temperature

• 0 to 90 percent RH, non-condensing
Accuracy

• Calibration accuracy and sensor conformity: ±0.1 percent

of span, ±1°C @ the calibrated ambient temperature and rated line voltage

• Type S, 0.2 percent

• Type T, below -50°C; 0.2 percent

• Calibration ambient temperature @ 25°C ±3°C (77°F ±5°F)

• Accuracy span: 540°C (1000°F) minimum

• Temperature stability: ±0.1°C/°C (±0.1°F/°F) rise in ambient maximum
Agency Approvals

• cULus

®

UL/EN/CSA C22.2 No. 61010-1 Listed File E185611

• cULus

®

ANSI/ISA 12.12.01-2007, CSA-C22.2 No.213-1987, Class 1 Division 2 Groups A, B, C

and D, Temperature Code T4A, File E184390 (optional)

• UL

®

50, 4X indoor locations, NEMA 4X, IP66 front seal

• CSA C22.2 No. 24 File 158031 (1/32 and 1/16 DIN sizes)

• CE, RoHS by design, W.E.E.E.

• SEMI F47-0200
Controller

• User selectable heat/cool, on-off, P, PI, PD, PID or alarm action

• Auto-tune control algorithm

• Control sampling rates: input = 10Hz, outputs = 10Hz

• Input and output capacity per controller type ordering information
Serial Communications

• Isolated communications

• Standard Bus Configuration Protocol
Wiring Termination—Touch-Safe Terminals

• Input, power and controller output terminals are touch safe removable 12 to 22 AWG

• Use 75°C, Cu conductor only