Setup menu – Watlow EZ-ZONE PM Express User Manual
Page 23
EZ-ZONE PM Express (PID)
• 23 •
Setup Menu
Setup Menu
Display
Parameter Name Description
[LoC]
[LoC]
Lockout Menu
Set the security clearance level. The user
can access the selected level and all lower
levels.
Appears if: Always
[Sen]
[ SEn]
Sensor Type
Set the analog sensor type to match the
device wired to this input.
Appears if: Always
[Lin]
[ Lin]
Linearization
Set the linearization to match the thermo-
couple type wired to this input.
For example, select [```H] for a type K
thermocouple.
Appears if: Sensor Type is set to Thermo-
couple.
[``t;C]
[ t.C]
Thermistor Curve
Select a curve to apply to the thermistor
input.
[``r;r]
[ r.r]
Resistance Range
Set the maximum resistance of the thermis-
tor input.
[`dEC]
[ dEC]
Decimal
Set the precision of the displayed value.
Appears if: Always
[`C_F]
[ C_F]
Display Units
Select which units will be displayed.
Appears if: Always
[r;Lo]
[ r.Lo]
Range Low
For process signals, this value scales the units
to minimum electrical units (0 volts or 4 mA)
Appears if: Always
[r;hi]
[ r.hi]
Range High
For process signals, this value scales the
units to maximum electrical units (10 volts
or 20 mA)
Appears if: Always
Range
(Defaults are shown bold)
1 to 5
1 Operations Menu (read only, A/M button disabled)*
2 Operations Menu (A/M button disabled, Set point R/W)*
3 Operations Menu (A/M button enabled, Set point R/W, Control Mode R/W)*
4 Operations Menu R/W access*
5 Operations Menu and Setup Menu full R/W access
*You can change the security level at any level
[``tC]
Thermocouple, [uolT] Volts dc, [`MA] Milliamps dc
[r0;1H]
RTD 100 Ω, [thEr] Thermistor
[`b]
B
[`J]
J
[`t]
T
[`c]
C
[`H]
K
[`d]
D
[`n]
N
[`e]
E
[`r]
R
[`f]
F
[`S]
S
[```A]
Curve A, [```b] Curve B, [```C] Curve C
[CUSt]
Custom
[```5]
5K, [``10] 10K, [``20] 20K, [``40] 40K
[```0]
Whole, [``0;0] Tenths, [`0;00] Hundredths
[```F]
°F
[```C]
°C
-1,999.000 to 9,999.000
0.0
-1,999.000 to 9,999.000