Watlow EZ-ZONE PM Express User Manual
Page 10
![background image](/manuals/359075/10/background.png)
EZ-ZONE PM Express (PID)
• 10 •
Install and Wire
Terminal Definitions
Slot C
Terminal Function
Model
98
99
power input: ac or dc+
power input: ac or dc-
PM _C_ _ _ - AAAAB _ _
CF
CD
CE
Standard Bus EIA-485 common
Standard Bus EIA-485 T-/R-
Standard Bus EIA-485 T+/R+
PM _C_ _ _ - AAAAB _ _
Slot A
Input 1
T1
S1
R1
(RTD) or current +,
(RTD), thermocouple -, current - or volts
-, thermistor
S1 (RTD), thermocouple + or volts +,
thermistor
Universal Sensor
input 1: all configurations
Outputs
Terminal Function
Configuration
1
2
X1
W1
Y1
common (Any switched dc output can
use.)
dc- (open collector)
dc+
Switched dc/open collector, output 1:
PM _C_ (C) _-_ AAAB _ _
W2
Y2
dc-
dc+
Switched dc, output 2:
PM _ C _ _ (C) - _ AAAB _ _
F1
G1
H1
voltage or current -
voltage +
current +
Universal Process, output 1:
PM _ C _ (F) _ - _ AAAB _ _
L1
K1
J1
normally open
common
normally closed
Mechanical Relay 5 A, Form C, output 1:
PM _C_ (E) _-_ AAAB _ _
L2
K2
normally open
common
NO-ARC 15 A, Form A, output 2:
PM (4, 6, 8, 9) C _ _ (H) - _ AAAB _ _
L2
K2
normally open
common
Mechanical Relay 5 A, Form A, output 2:
PM _C_ _ (J) -_ AAAB _ _
L1
K1
L2
K2
normally open
common
Solid-State Relay 0.5 A, Form A
output 1: PM _C_ (K) _ - _ AAAB _ _