Installation prerequisites for standards
•
UL listed products
•
c-UL listed products
•
Product List
UL/c-UL File No.: E220851
For the detailed certification's information, refer to the Pro-face Home page.
Be aware of the following items when building the PS-A into an end-use product:
•
The PS-A unit’s rear face is not approved as an enclosure. When building the PS-A unit into an end-use product, be
sure to use an enclosure that satisfies standards as the end-use product’s overall enclosure.
•
The PS-A unit must be used indoors only.
•
Install and operate the PS-A with its front panel facing outwards.
•
If the PS-A is mounted so as to cool itself naturally, be sure to install it in a vertical panel. Also, it’s recommended that
the PS-A should be mounted at least 50 mm away from any other adjacent structures or machine parts. The tempera-
ture must be checked on the final product in which the PS-A is installed.
•
For use on a flat surface of a Type 4X (Indoor Use Only) and/or Type 12 Enclosure.
The safety certificate can be downloaded from Pro-face Home Page.
Home Page URL
http://www.pro-face.com/
CE Marking
PS3450A-T41 units are CE marked, EMC directives and Low Voltage Directive compliant products.
PS3450A-T41-24V and PS3451A-T41-24V units are CE marked, EMC directives compliant products.
For the detailed information on CE Marked, be downloaded and refer the Declaration of Conformity from Pro-face Home
Page.
Home Page URL
http://www.pro-face.com/
Industrial Control Equipment
refer to UL508
see [a] in the
“Product List“
Process Control Equipment
refer to CSA-C22.2
No.142
see [b] in the
“Product List“
Product Model No.
Registration Model No.
UL
c-UL
[a]
[b]
PS3450A-T41
3581702-01
9
9
PS3450A-T41-24V
3581702-11
9
9
PS3451A-T41-24V
3581702-12
9
9