7• input circuit output specifications – Proface LT3300 - 5.7 All-in-One HMI" User Manual
Page 7
7
• Input Circuit
Output Specifications
Output Terminal
OUT0 to OUT3
OUT4 to OUT15
Rated Voltage
DC24V
Allowable Voltage Range
DC20.4V to DC28.8V
Output Method
LT330
∗-∗1-D24-K
Sink Output
LT330
∗-∗1-D24-C
Source Output
Maximum Load Voltage
0.2A /point, 1.6A /common
Min. Load Current
1mA
1mA (Pulse/PWM out-
put unavailable)
Output Voltage Drop
DC0.5V or less
Output Delay
Time
OFF to ON
5
µs or less (With output
at DC24V, 200mA)
0.5ms or less (With
output at DC24V, 200mA)
ON to OFF
5
µs or less (With output
at DC24V, 200mA)
0.5ms or less (With
output at DC24V, 200mA)
Voltage Leakage (when OFF)
0.1mA or less
Clamp Voltage
39V ± 1V
Type of Output
Transistor Output
Common Lines
2
Common Design
8 points/1 common line x2
External Connection
38-pin connector (also used for Input)
Output Protection Type
Output is unprotected
Internal Fuse
3.5A, 125V Chip fuse x2 (not replaceable)
Surge Control Circuit
Zener diode
Output Points
16
Output Signal Display
No LED indicators
Status Display Element
None
Isolation Method
Photocoupler Isolation
External Power Supply
For Signal: DC 24V
DC 24V
External Power
Internal Circuit
Internal Circuit
COM B9
+
-
IN15 A8
- +
*1
*1 Dotted line shows
connection to sink
output type.
IN14 B8
IN13 A7
IN12 B7
IN11 A6
IN10 B6
IN9 A5
IN8 B5
IN7 A4
IN6 B4
IN5 A3
IN4 B3
IN3 A2
IN2 B2
IN1 A1
IN0 B1