Installations, Installation requirements, Lt installation – Proface LT3300 - 5.7 All-in-One HMI" User Manual
Page 10
10
Installations
1.
Installation Requirements
• For easier maintenance, operation, and
improved ventilation, be sure to install the
LT at least 100 mm [3.94 in.] away from
adjacent structures and other equipment.
• Be sure that the surrounding air temperature
and the ambient humidity are within their
designated ranges. (Surrounding air tempera-
ture: 0 to 50
°C, Ambient humidity: 10 to
90%RH, Wet bulb temperature: 39
°C max.)
When installing the LT on the panel of a cab-
inet or enclosure, “Surrounding air tempera-
ture” indicates both the panel face and
cabinet or enclosure’s internal temperature.
• Be sure that heat from surrounding equip-
ment does not cause the LT to exceed its
standard operating temperature.
2.
LT Installation
(1) Create a Panel Cut following the dimen-
sions in the table below.
(2) Confirm that the installation gasket is
attached to the LT unit and then place the
LT unit into the Panel from the front.
• It is strongly recommended that you use
the installation gasket, since it absorbs
vibration in addition to repelling water.
For the procedure for replacing the
installation gasket, refer to “LT3000
Series Hardware Manual”.
(3) The following figures show the four (4)
fastener insertion slot locations. Insert
each fastener’s hook into the slot and
tighten it with a screwdriver. Insert the
installation fasteners securely into the
insertion slot recess.
100
[3.94]
100
[3.94]
100
[3.94]
100
[3.94]
Unit:
mm[in.]
100
[3.94]
100
[3.94]
100
[3.94]
Panel Face
Inside Cabinet
Unit: mm [in.]
X
r
≤
3[0.12]
Panel
thickness
LT
Y
LT
X
Y
Panel
thickness
LT-
3300
Series
156.0
[6.14
]
123.5
[4.86
]
1.6[0.06]
to
5.0[0.20]
+1
-0
+0.04
-0
+1
-0
+0.04
-0
Bottom
Insertion
Slots
Top
Insertion Slot Recess
Hook the fastener
on the Recess,
Panel
Installation Fastener
Hook
and secure the fastener
on the panel with a
screw.
LT
Panel