beautypg.com

Maple Systems HMI5000L Series User Manual

Page 12

background image

12

HMI5000L Installation Guide

1010-1018 Rev 01 www.maplesystems.com

Figure 4: HMI Power Wiring

To connect the HMI to power:

1. Connect the power cable to the HMI.

a. Strip the power cable shield to expose 2” of the black and

red wires.

b. Strip about ¼” of insulation from the black and red wires.

c. Connect the red wire to the 24V DC positive (+) input of the

HMI power terminal block.

d. Connect the black wire to the 24V DC negative (–) input of

the HMI power terminal block.

e. Connect the power cable shield wire to the HMI power

terminal block’s chassis ground input.

2. Route the power cable to the HMI power supply. The power

cable should not be any longer than necessary.