Maple Systems OMI5100A-CE User Manual
Page 14
14
OMI5000 Series Installation Guide
1010-1013 Rev 01 www.maplesystems.com
Maintenance
Figure 6: DIP switch positions (power must be cycled on the OMI to enable the DIP
switch mode).
SW1
SW2
SW3
SW4
Mode
ON
OFF
OFF
OFF
Touchscreen Calibration mode
OFF
ON
OFF
OFF
Reserved
OFF
OFF
ON
OFF
Force into Boot Loader mode
OFF
OFF
OFF
ON
Reserved
OFF
OFF
OFF
OFF
Normal operation
Touchscreen Calibration mode: This mode allows you to recalibrate
the touchscreen.
Boot Loader mode: This mode forces the OMI to not execute the
project. This mode is used when replacing or reinstalling the operating
system. Contact Maple Systems for more information.
Normal Operation: All DIP switches must be in the OFF position for
normal operation.
Fusing Requirements
If the display does not come on within two seconds of power up, remove
power. An internal fuse will prevent damage if the polarity of the DC
power is incorrect. Check wiring to insure proper connections and try to
power up again.
Serial Port Connections
The diagrams below indicate the proper pin connections for the serial
ports of the OMIs.