beautypg.com

Troubleshooting checklist – Warner Electric CB Series and Super CB Series Sizes 2, 4, 5, 6 and 8 User Manual

Page 7

background image

7

Warner Electric • 800-825-9050

P-258 • 819-0406

Troubleshooting Checklist

The actuator is simply a mechanical linkage. When the actuator does not function, the following inspection
should be made.

Possible Problem

Recommended Action

1. No power going to the coil (check

w/voltmeter).

A. Check all wiring and switching in the system that supplies power to the

clutch coil, and ensure its continuity.

B. If wiring is correct, inspect to see if power is coming from the power

supply. If there is no power from the power supply, check switching or

programming and/or replace power supply as necessary.

2. Lack of continuity in coil windings

(check w/ohmmeter).

Check the continuity of the clutch coil windings by using an ohmmeter, and

replace the coil if necessary. After the coil is replaced, ensure it is properly

aligned as described in Step 3A below.

3. Mechanical binding of plunger.

A. Realign coil. As shown in Figure 5, with the coil energized, apply light

pressure to the opposite side of the control collar, and set the

actuator/cam tip clearance (airgap) at .010'' to .030''. Note: For AC

coils with an actuator limit stop (ALS) option, the actuator should hit the

ALS and bottom simultaneously.

B. If Step 3A fails to resolve the problem, replace the coil assembly and

perform Step 3A again to realign the coil.

4. Actuator does not clear the cam stop

Realign coil as in Step 3A above.

5. Collar pushes so hard on the actuator

that the coil is unable to pull in.

A. Actuator loading can be caused by the braking force exceeding the

capacity of the brake spring. Confirm the application criteria and re-

evaluate the unit size for this application.

B. If the spring differential setting is too large, the clutch spring could be

opening into the control collar and acting as a brake. In this case, the

spring differential must be reset (See Section 5 “CB Spring Differential

Adjustment”).

C. If the coil has been replaced with an air cylinder, ensure that the cylinder

is square to the collar and that the actuator has the proper travel.

Inspect the air source and supply to ensure the cylinder is receiving air

when appropriate.