ATO-400P / ATO-600P Operating Procedures

31

Table 8.0 Review Record Procedure (continued)

STEP

ACTION

ATO DISPLAY

8-5

Part of the selected record’s ID appears
displaying the record number,
MANUFACTURER, and MODEL. Press the
“ENTER” key to display the number of tests
in the record, the date, and the time of the
selected tests.

8-6

Pressing the “ENTER” key will list all test
#1 data: Test current, burn-in time, and the
measured resistance value.

NOTE

The test record in this example contains 2
tests.

8-7

Press

?

key to advance to next test. Press

?

key to return to previous test.

8-8

Press STOP to return to START MENU.

Display returns to START MENU

.

This completes the Review Record Procedure.

TEST NUMBER: 1

TEST CURRENT: 100.2A
BURN - IN TIME: 5 Sec

500.3 MICRO-OHMS

TEST NUMBER: 2

TEST CURRENT: 50.6A
BURN - IN TIME: 5 Sec

500.1 MICRO-OHMS

2 TESTS

04/11/05 17:27:00