The PRO-Alert™ Refrigerant Leak Detector is design certified by MET Laboratories, Inc.
to meet SAE J1627, "Rating Criteria for Electronic Refrigerant Leak Detectors" for R-12,
R-22 and R-134a. The following SAE Recommended Practice applies to this instrument
and to the use of generally available electronic leak detection methods to service motor
vehicle passenger compartment air conditioning systems.
1. The electronic leak detector shall be operated in accordance with these
operating instructions.
2. Leak test with the engine not in operation.
3. The A/C system should be charged with sufficient refrigerant to have a gauge
pressure of at least 50 PSI (340 kPa) when not in operation. At temperatures below
59°F (15°C) leaks may not be measurable, since this pressure may not be reached.
4. Take care not to contaminate the detector probe tip if the part being tested is
contaminated. If the part is particularly dirty, it should be wiped off with a dry shop
towel or blown off with shop air. No cleaners or solvents should be used, since
electronic detectors are sensitive to their ingredients.
5. Visually trace the entire refrigerant system and look for signs of air conditioning
lubricant leakage, damage and corrosion on all lines, hoses and components. Each
questionable area should be carefully checked with the detector probe as well as all
fittings, hose-to-line couplings, refrigerant controls, service ports with caps in place,
brazed or welded areas, and areas around attachment points and hold-downs on
lines and components.
6. Always follow the refrigerant system around in a continuous path so that no areas of
potential leaks are missed. If a leak is found, always continue to test the remainder
of the system.
7. At each area checked, the probe shall be moved around the location at a rate no
more than 1 to 2 inches/second (25 to 50 mm/second) and no more than 1/4 inch
(5 mm) from the surface completely around the position. Slower and closer
movement of the probe greatly improves the likelihood of finding a leak.
8. An apparent leak should be verified at least once by blowing shop air into the area of
the suspected leak, if necessary, and repeating the check of the area. In cases of
very large leaks, blowing out the area with shop air often helps locate the exact
position of the leak.
9. Leak testing of the evaporator core while in the air conditioning module should be
accomplished by turning the air conditioning blower on high for a period of
15 seconds minimum, shutting it off, then waiting for the refrigerant to accumulate in
the case for the time specified in step 10, then inserting the leak detector probe into
the blower resistor-block or condensate drain-hole if no water is present, or into the
closest opening in the HVAC case to the evaporator, such as the heater duct or a
vent duct. If the detector emits an alarm signal, a leak apparently has been found.
10. The accumulation time for evaporator testing is 13 minutes.
11. Following any service to the refrigerant system of the vehicle, and any other service
which disturbs the refrigerant system, a leak test of the repair and of the service
ports of the refrigerant system should be done.