Optional boards, Transmitter module (4xtm - notifier), Led interface module (4xlm - notifier) – System Sensor PDRP-1002 User Manual
Page 8: Zone relay module (4xzm - notifier)

1 The PDRP-1002/PDRP-1002E
Transmitter Module (4XTM - NOTIFIER)
8
The PDRP-1002 PN 51135:A 03/11/99
Optional Boards
The PDRP-1002/PDRP-1002E has mounting slots for two option boards. Any two of
the three option modules may be installed.
Transmitter Module (4XTM - NOTIFIER)
The Transmitter Module provides a supervised output for
local energy municipal box transmitter (for NFPA 72
Auxiliary Fire Alarm System) and alarm and trouble
reverse polarity circuits (for NFPA 72 Remote Station Fire
Alarm System). Also included is a DISABLE switch and
disable trouble LED.
As a jumper option, the alarm reverse polarity circuit will
open on trouble if no alarm exists.
LED Interface Module (4XLM - NOTIFIER)
The LED Interface Module supports the RZA-4X Remote
Annunciator module. Annunciator wiring is supervised for
open conditions by this module. The Annunciator Driver
Module mounts to the main board, occupying one of the
two option connectors.
Zone Relay Module (4XZM - NOTIFIER)
The Zone Relay module provides Form-C contacts for the
following:
As a jumper option, the first four relays described below can
be made silenceable.
DIP 1=OFF
Either Zone
DIP 1=ON
Cross Zone
If Supervisory (DIP 2=ON)
Either Zone
Cross Zone
Alarm Detected
First Alarm
Alarm Detected First Alarm
Alarm Detected
Second Alarm Alarm Detected Second Alarm
Release 1
Release 1
Release
Release
Release 2
Release 2
Not Used