Remote control and monitoring function settings, Maintenance – IDEC High Performance Series User Manual
Page 1161

WindO/I-NV2 User’s Manual
27-3
1 Web Server Function (HG2G-5F, HG3G/4G)
27
Maintenance
●
Remote Control and Monitoring function settings
1
On the Configuration tab, in the System Setup group, click Project.
The Project Settings dialog box is displayed.
2
Configure the items on the Web Server tab.
■
Disable Web Server function
When the web server function is disabled, the web page for the IP address held by the display is not displayed, even
when accessed.
(Default: Off)
■
Remote Control and Monitoring
Enables and disables remote monitoring and remote control. (Default: Disable)
■
Execution Interval
Specifies the interval (0 to 5000) for the HG2G-5F, HG3G/4G to return data.
When the remote control function and the remote monitoring function place a load on HG2G-5F, HG3G/4G operation,
that load can be reduced by increasing this value.
However, the display update speed in the web browser will become slower. (Default: 5 (= 50 ms))
■
Port No.
Specifies the port number to use for the web server function. (Default: 80)
3
Click the OK button.