R.

All zones served by a SlimZone control module should have the same basic load characteristics
(i.e., do not put 4 zones on an east exposure, and the 5th zone on a southwest exposure).

S.

All references to typical dampers refer to Enerstat model dampers.

T.

Zones 14-19 adhere to the same schedule and act as a single call for equipment. Although they
are separate physical zones they act as a single zone when communicating with the SZP
Control module. It is recommended that when considering the layout of your zone system,
zones 14-19 should be assigned to areas of low priority.

3.

COMPONENT REQUIREMENTS

3.1

BASIC SYSTEM

The basic system consists of the main SlimZone Premier Control module (SZP-3: 3 zone
module) and its supporting components.

ITEM

QUANTITY

CONSIDERATIONS

SZP-3 control module

one (1)

contains three (3) zones

DSL-520P zone thermostat

one (1) per zone

use standard nonshielded 4
conductor 18-24AWG copper wire

Motorized zone dampers

one (1) per zone (minimum)

use standard nonshielded 3
conductor 18AWG copper wire

24VAC transformers

one (1) for main module

75VA

zone dampers powered by

refer to section 3.4 for sizing

separate transformer(s)

Table 3.1: SlimZone Premier Basic Components

3.2

EXPANDER MODULE

Each SlimZone Expander module (SZEX) consists of two (2) additional zones. For each
expander module added, the following items are required:

ITEM

QUANTITY

CONSIDERATIONS

SZEX expander module

one (1)

contains two (2) zones

DSL-520P zone thermostat

one (1) per zone

use standard nonshielded 4
conductor 18-24AWG copper wire

Motorized zone dampers

one (1) per zone (minimum)

use standard nonshielded 3
conductor 18AWG copper wire

24VAC transformers

SZEX powered by SZP

N/A

zone dampers powered

refer to section 3.4 for sizing

by separate transformer(s)

Table 3.2: SlimZone Expander Module Components

Note: Expander module itself does not require a transformer as it is powered by the control