D. Go to the Equipment Test screen (Figure 5.2). Following the menus, turn each equipment
output relay ON and OFF to check that on-board relays are functional.
E. Go to the Zone Module test screen. Activate all zone dampers and perimeter heat relays (if
perimeter heat option installed).
F. Go to the Environmental test screen and activate the bypass damper.
NOTE: Leave the bypass damper closed at this stage.
G. Go to the Panel Setup screen and configure the control module according to your
installation.
NOTE: During the panel setup, you must select a Must-Service zone. An equipment call
from this zone is given enough weight to activate first stage. You may want to select a zone
at close proximity to the panel during the system test to facilitate the equipment cycle test.
H. Connect RH & RC terminals to power the equipment relays.
I. Go to the Schedule menu and select Schedule: Normal.
J. Go to the Main Menu:
K. Observe that all zone damper LEDs come ON and that all zone dampers are open.
SlimZone Premier
23
Equipment
Zone Module
Environmental
Equipment
Zone Module
Environmental
For HVAC Techs Only!
Setup
Equipment Test
Locked
3
1
Equipment
Zone Module
Environmental
Outdoor
73 Duct 74
Pressure 0.03 in. WC
Bypass - Normal
3
For HVAC Techs Only!
Setup
Equipment Test
2
Setup
Panel
Bypass
2
System Type:
Heat pump
12:00A Fri Jan01/99
System Off
Fan On
Schedule:Suspended
Suspended
4
Options
Schedule: Suspended
Programming
2
Schedule: Normal
4
1
Equipment Relay
W4 Off
W3 Off
4
Damper #01
Open
Perimeter Heat #01
Off
12:00A Fri Jan01/99
System Off
Fan On
Schedule: Normal
2
Zone #01 Room 76
Heat 68 Cool 70
Auto Mode
Calls: Fan
Press or to select zone
Refer to Figure 5.3
Press button to
toggle damper position
Zone #01
Exercise Damper
Perimeter Heat
1
2
3
3
Press until
Normal is selected
Select the following:
- System Off mode
- Fan On to enable constant fan
1
Note: Must hold button for 10 seconds to unlock these menu options.