Robertshaw SlimZone PREMIER ZONE CONTROL SYSTEM User Manual
Page 28

N. Go to the Bypass Setup screen and initiate the setup sequence. Note that this process
may take up to approximately 5 minutes and you cannot abort this sequence.
O. Go to the Programming menu and program all temperature setpoints and schedules for
each zone. Refer to section 5.2 for programming features.
P. Return to the Main Menu. System is ready to operate. Place the system mode of operation,
fan control, and schedule to the desired settings.
SlimZone Premier
25
Setup
Panel
Bypass
3
2
Are you sure ?
Yes
No
Bypass setup
Step 06
Wait 30
You may abort the
sequence here.
See also other documents in the category Robertshaw Water boiler:
- 800 (2 pages)
- 9400 (2 pages)
- 9401 (12 pages)
- 9400 (11 pages)
- 9405 (2 pages)
- 9405 (12 pages)
- 9415 (2 pages)
- 9415 (12 pages)
- 9500 (2 pages)
- 9500 (11 pages)
- 9505 (2 pages)
- 9505 (11 pages)
- 9520 (2 pages)
- 9520 (12 pages)
- 9550 (2 pages)
- 9555 (2 pages)
- 9555 (12 pages)
- 9560 (2 pages)
- 9600 (2 pages)
- 9600 (12 pages)
- 9610 (2 pages)
- 9610 (12 pages)
- 9615 (2 pages)
- 9615 (12 pages)
- 10-531 TAP-1 Adaptor (1 page)
- 200 SERIES (2 pages)
- 300-201 (2 pages)
- 300-202 (2 pages)
- 300-203 (2 pages)
- 300-204 (2 pages)
- 300-205 (2 pages)
- 300-206 (2 pages)
- 300-207 (2 pages)
- 300-208 (2 pages)
- 300-227 (2 pages)
- 300-229 (2 pages)
- 400 SERIES (2 pages)
- 8400-1 (2 pages)
- 8405-1 (12 pages)
- 8406-1 (12 pages)
- 8425-1 (2 pages)
- 8600-1 (2 pages)
- 8601-1 (12 pages)
- 8625-1 (14 pages)
- 900 SERIES (2 pages)