beautypg.com

Operation, Ransburg, High voltage on control sequence – Ransburg Voltage Master 2 78789_LEPS5001 User Manual

Page 28: High voltage off control sequence, Overload sequence

background image

OPERATION

Reference the control panel schematic in Figure

5, the power supply schematic in Figure 14 and

any system installation drawings.

The following explanations assume that all ex-

ternal interlocks or jumpers are installed and

that the power supply is operating normally. The

following is intended for those that have a basic

understanding of electrical circuits and schematics.

HIGH VOLTAGE ON

CONTROL SEQUENCE

When the front panel HV ON/OFF momentary

switch or external HV ON signal (PLC or push-but-

ton) is supplied across terminals TB2-3 and TB2-5,

voltage is supplied to the CR1 coil through the

Master Control circuit board interlock (J3-1 &

J3-4) and one set of normally closed (NC) CR3

contacts. Voltage is also supplied through a series

of interlocks, pressure switch(es), and operator

controls, depending on the system installation

requirements, to CR2 and the HV ON lamp, any

of which will turn HV OFF or not allow HV to be

turned ON if broken. The voltage supplied to

CR1 energizes the coil causing NO CR1 contacts

(#11 to #12) to close, which then energizes the

CR2 coil and the HV ON indicator. Activation of

CR2 then causes one set of NO CR2 contacts to

close (#11 to #12) which latches the CR2 coil ON.

Another set of NO CR2 contacts supply voltage

from a set of NC CR3 contacts through the Motor

Control PCB interlock (J2-5 to J2-6) to the variable

control transformer (VAT1). VAT1 then supplies

AC voltage to the Power Supply via TB4 and then

through the control cable (supplied as part of the

power supply).

The overload circuit is activated upon application of

a momentary HV ON contact closure across wires

#3 and #5. When the contact closure opens, the

inhibit timer keeps the overload circuit disabled

for approximately 3-4 seconds, allowing the power

supply to reach normal operating voltage without

causing nuisance or unpredictable overloads at

start-up. The LED, located on the Master Control

board (see Figure 10), indicates that the inhibit

condition is active.

HIGH VOLTAGE OFF

CONTROL SEQUENCE

When the front panel HV ON/OFF/RESET, external

pushbutton, external interlock, or external PLC

HV OFF opens the circuit to wire #10, voltage is

removed from the coil of CR2. Thus, the NO CR2

contacts open and remove voltage from VAT1 to

the power supply and the HV ON indicator.

OVERLOAD SEQUENCE

The current return from the power supply tank is

compared to the overload setting within the Master

Control board circuit. If the actual output current

exceeds the overload setting, then a set of the

Control board overload relay contacts open (wire

#10 to J3-25, 27) disconnecting voltage from the

CR2 coil through the latched CR2 contacts (wire

#11 to #12) to VAT1 and therefore the power supply

tank. Another set of Control PCB overload contacts

close (wire #10 to #15) supplying voltage to the

CR3 coil, HV OL light, Horn, and external alarm.

One set of NO CR3 contacts (wire #10 to #15)

will then latch CR3 ON until a RESET command

is given which removes voltage at wire #10 and

therefore the CR3 coil. Another set of NC CR3

contacts open to ensure that the CR1 coil cannot

be energized again with a HV ON command until

a HV RESET (HV OFF) command has first been

received.

Voltage Master 2 - Operation

24

Ransburg

CP-02-02.6