Maintenance

37-O 4/00

Problem

Cause

Remedy

Burner backfires

8. Loose Oil Fittings

Check all fittings and tighten.

(cont.)

9. Plugged Oil Filter

Check and clean or replace.

10. Plugged screen in

Check and clean or replace.

oil pump

11. Plugged Flue

Check flue to see if it is plugged. Check draft at
flue. Clean.

12. Vacuum on pump

Check for too high a vacuum on the pump. Check oil lines
and distance from tank to boiler. Repair or replace as
necessary.

13. Hole in suction line

Check and replace as necessary.

Boiler will not

1. Oil Supply

Check oil level in supply tank to be sure it is not

maintain pressure

below intake line. Fill tank with oil. Check for
clogged nozzle. Clean or replace. Check oil filter and
replace if necessary.

2. Oil Nozzle

Check for clogged nozzle. Clean or replace.

3. Oil Valve

Check voltage between oil valve leads at terminal block to
be sure oil valve is getting power.

4. Oil Pump

Check for clogged strainer or filter. Remove
and clean. Check for slipping or broken coupling. tighten or
replace. Check for frozen pump shaft. Replace.

5. Pressuretrol

Disconnect all power to the controller. Disconnect the
wires from the controller. Connect an ohmmeter between
the switch terminals. Lower the set point of the controller.
Switch should make. Raise the set point and re-check
ohmmeter. Switch should break. If the controller operates
improperly, replace it.

6. Scale built-up in boiler

Call water treatment professional and consult factory.

7. Refractories

Check refractories to see if they are cracked or
broken in pieces. Replace as necessary.

8. Steam traps

Check traps to see if they are clean or replace as

blowing through

necessary.

Boiler is Surging

1. Steam traps

Check traps to see if they are clean or replace as

blowing through

necessary.

2. Perc (cleaning solvent

Clean boiler with washing soda per

in Boiler)

instruction manual.

3. Scale build-up or lime

Call water treatment professional and consult factory.

deposits