Description/instructions, Condensate return tank – Fulton Classic ICX or FB-F Vertical Tubeless Boilers (Steam) Oil Fired User Manual
Page 17
![background image](/manuals/345503/17/background.png)
Description/Instructions
Vent
Vent
Return
Check
Valve
Shut
Off
Valve
Cold
Water
Supply
Cold Water
Inlet
Sight
Glass
Union
Pump/
Strainer
Thermometer
Aquastat
Drain
Outlet
To Drain
Condensate
Return
Tank
Basic Boiler,
Condensate Tank,
and Blow off
Separator
Note
Where a condensate return tank is
to be fitted, this should:
1) Be vented and
2) Have a capacity sufficient to
satisfy boiler consumption as well
as maintain proper return tank
temperature.
3) Vent pipe should not be down-
sized (This may cause pressure
build up in the condensate tank.)
4) Return pipes must not be insu-
lated. This can cause overheating
the return system, causing a vapor
lock in the pump.
5) See Return System Instruction
Manual for detailed instructions.
Note
Care should be taken to ensure
that the blow off receptacle used
meets the regulations covering
such vessels. If in doubt consult a
Fulton Representative for advice.
9-O 4/00