Section 3 – Operation

1. Start-Up Preparation & Installation Review

a) Check with local authorities where approval for start-up is required. In some localities,

final inspection of services may be required.

b) Review the installation section of this manual carefully. Confirm accordance with

installation guidelines, including:

1. In general, ensure that the heater area is in conformance with

established heater room requirements. Review national and local codes.

2. Preparation

a) Check for total absence of water in pipework and fluid. To help the system, open all

drains; blow air nitrogen if available into a high point bleed through a pressure regulating

valve.

Note

Unless specially filtered, compressed air will introduce moisture into the system.

Dry air or Nitrogen is recommended.

b) Make sure that there are no obstructions left in the thermal fluid circuit from pressure leak

testing such as blanking plates in flanged joints.

c) Check that pipework is free to expand naturally when hot. Open all valves to user circuits

including air bleed valves at high points and drains at low points in the piping system, and

the liquid level test connections in the expansion section of the combination tank.

3. Filling the System

a) The viscosity of thermal fluid is generally very high (500 cS) at ambient temperature.

Below 50°F (10°C) some fluids become very thick. Fluid should be in a pumpable liquid

form prior to filling the system.

b) Filling must be carried out from the lowest point in the system in order to prevent air

pockets from forming.

c) A drain and fill point (generally a 3/4” threaded coupling) is provided on the inlet to the

pump suction on skid-mounted units. Typically a portable, high velocity pump, such as

the type used for chemical transfer, is appropriate for filling the system. Where only one

or two drums of fluid are required, a handheld pump may be practical.