Fulton Vertical Electric (FT-N) Thermal Fluid (hot oil) Heater User Manual
Page 20
Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423
Page 20
d) Typical Fulton Thermal Piping Schematic
e) Alignment
1. Proper alignment directly affects bearing, coupling, and seal life
expectancy. The pump is properly aligned before it leaves the factory.
Because the system expands in operation, pump must be realigned
when the system is at operating temperature.
2. The coupling alignment of the pump and driver must be carefully
checked for angular and axial alignment. Check pump manufacturers
instructions for these specifications. The use of a dial indicator to check
the axial and angular alignment is recommended.
20
23
1.
Thermal Fluid Heater
2.
Thermal Fluid Circulating Pump
3.
Safety Relief Valve
4. Thermometer
5. Pressure
Gauge
6.
Thermal Fluid Heated Equipment
7.
Bypass Valve to maintain full flow to heater
8.
Expansion Joints as required
9.
Anchor and Pipe Guides as required
10. Expansion
Tank
11. Vent Piping should be full size of expansion tank vent
12. Deaerator
Tank
13. Deaerator Tank inlet must be highest point of piping
14. Thermal Buffer Tank
15. Catch Tank for drain of pressure relief valve, cold seal,
expansion tank, and vent. Locate in safe area.
16. Gate
Valve
17. Strainer
18. ¾” System Fill Connection
19. Flexible Connection as necessary
20. Isolating Valve as necessary
21. Manual Low Level Test Line
22. Manual High Level Test Line
23. Buffer
Drain
Full pump design flow must be maintained at all
times thru the main piping loop. Low flow will
seriously damage heater.
Note: Manifold configuration for illustration only.
See drawing appropriate to particular model.