Fulton Vertical Electric (FT-N) Thermal Fluid (hot oil) Heater User Manual
Page 10

Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423
Page 10
Note
Do not use system circulating pump for system filling.
Note
A pump that has been used for water or a different thermal fluid should not be used prior to
extensive cleaning. Thermal fluid can be damaged by contact with moisture or other fluids.
Warning
Pressurizing a drum to force fluid into the system is not recommended. The drum can easily
explode, creating a hazard to personnel and equipment.
Note
Tanks are non-code as a standard. Non-code tanks cannot be pressurized over 15psig. Tanks built
to ASME code Section VIII Div 1 are available upon request.
Note
Do not run the pump before filling it with fluid.
Caution
1.
Use extreme caution opening plug when system temperature is elevated.
2.
Wear eye and hand protection.
3.
Back the plug out slowly to the last two or three threads. Allow any pressure under
plug to bleed slowly to prevent a spray of hot oil.
Note
Flash steam may be generated at any point up to the operating temperature. Watch for gauge
fluctuations.
Note
All of the above maintenance procedures should be completed by trained personnel. Appropriate
training and instructions are available from the Fulton Service Department at (315) 298-7148 or
your local Fulton Thermal Representative.