beautypg.com

Fulton Vertical Electric (FT-N) Thermal Fluid (hot oil) Heater User Manual

Page 29

background image

Fulton Thermal Corp.*Electric Thermal Fluid Heaters Manual* Version 2010-0423

Page 29

1. A wall-mounted, fused disconnect sized for the unit must be provided

and fitted by the client/contractor, if a disconnect is not supplied on the

panel.

2. Fuses must be sized according to motor name plates and local electrical

codes.

3. Heaters and single skid systems are generally shipped completely

prewired. The liquid level switch on the expansion tank, when supplied,

will be shipped in the parts box and must be installed in the field. Multiple

skid systems may require wiring between the skids.

4. If the unit is not skid-mounted at the factory, the client/contractor is

required to wire the circulating pump starter.

5. When using a SCR, a Shunt Trip Breaker is required to be installed by

the customer. It will be used to remove power to the panel in the event of

an over temperature/pressure condition. The Shunt Trip Coil needs to be

wired to the boiler electrical panel as indicated on the electrical drawing.

Note

If the circulating pump motor is not supplied by Fulton Thermal Corporation, the

motor starter will not be supplied.

o) Voltage & Frequency

1. Normal supply will be 460 volts, 3 phase, 60 Hz, AC unless otherwise

specified.

2. Make sure the information on the electrical drawing corresponds to your

voltage and frequency. Check the supply voltage and make sure that

there is no over-or under-voltage exceeding 10% of the nominal value.

11. Pipework Systems

a) Certain properties of thermal fluid, including low surface tension, make it necessary to

pay particular attention to containing the fluid. Good pipework system design, welded